| 2016-09-12 10:56:02 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE |
| | LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR, ALL LOW |
| | VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE |
| | ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE, |
| | WIRELESS SYSTEMS, ELEVATORS, KITCHEN HOOD, WALK-IN |
| | COOLERS, ETC. A NOTE WILL SUFFICE. |
| | 2. SHEET E1.0- PLEASE ADD A GENERAL NOTE TO SHEET TO |
| | INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE |
| | 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND |
| | THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE |
| | LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL |
| | SUFFICE |
| | 3. SHEET E1.0- ADD A NOTE TO MAINTAIN ALL ELECTRICAL |
| | EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE |
| | AND CITY REGULATORY AGENCIES. |
| | 4. PLEASE ADDRESS FIRE COMMENTS RELATED TO ELECTRICAL. |
| | 5. SHEET E2.0- FBC-E C405.5. INTERIOR LIGHTING POWER |
| | REQUIREMENTS. A BUILDING COMPLIES WITH THIS SECTION IF |
| | ITS TOTAL CONNECTED LIGHTING POWER CALCULATED UNDER |
| | SECTION C405.5.1 IS NO GREATER THAN THE INTERIOR |
| | LIGHTING POWER CALCULATED UNDER SECTION C405.5.2. |
| | PROVIDE A LIGHTING POWER DENSITY CHART TO SHOW |
| | COMPLIANCE. |
| | 6. SHEET E2.1- PLEASE SHOW COMPLIANCE WITH FBC EC |
| | 405.7- A MINIMUM OF 50% OF ALL 125V, 15 AND 20AMP |
| | RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED WHERE |
| | INSTALLED IN PRIVATE OR OPEN OFFICES AND CLASSROOMS. |
| | THIS INCLUDES MODULAR PARTITIONS. SEE EXCEPTIONS IN |
| | CODE LANGUAGE. |
| | 7. NEC 422.52 ELECTRIC DRINKING FOUNTAINS. ELECTRIC |
| | DRINKING FOUNTAINS SHALL BE PROTECTED WITH GROUND-FAULT |
| | CIRCUIT ?INTERRUPTER PROTECTION (GFI) AND BE READILY |
| | ACCESSIBLE. BREAKER AT PANELBOARD WILL SUFFICE, MARK |
| | PANELBOARD ACCORDINGLY. |
| | 8. RISER DIAGRAM AND PANEL SCHEDULES, PLEASE PROVIDE |
| | AVAILABLE FAULT CURRENT AVAILABLE AT THE FPL SERVICE. |
| | ATTACH TO DOCUMENTS LETTER FROM FLORIDA POWER & LIGHT |
| | INDICATING AIC. SHOW AIC CALCULATION BASED ON |
| | INFORMATION PROVIDED BY UTILITY FOR APPROVAL. NEC |
| | 110.24 FBC 107 |
| | 9. PROVIDE VOLTAGE DROP CALCULATIONS NOT ONLY FOR |
| | FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7 |
| | 10. SHOW ON ONE-LINE PUMP STATION SEWAGE LIFT FROM MDP |
| | PANEL. |
| | 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| | REGARDING THIS PROJECT. |
| | |
| | |