2016-09-12 10:56:02INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE
 LIGHTING AND ASSOCIATED EQUIPMENT, GENERATOR, ALL LOW
 VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE,
 WIRELESS SYSTEMS, ELEVATORS, KITCHEN HOOD, WALK-IN
 COOLERS, ETC. A NOTE WILL SUFFICE.
 2. SHEET E1.0- PLEASE ADD A GENERAL NOTE TO SHEET TO
 INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE
 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND
 THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE
 LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL
 SUFFICE
 3. SHEET E1.0- ADD A NOTE TO MAINTAIN ALL ELECTRICAL
 EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE
 AND CITY REGULATORY AGENCIES.
 4. PLEASE ADDRESS FIRE COMMENTS RELATED TO ELECTRICAL.
 5. SHEET E2.0- FBC-E C405.5. INTERIOR LIGHTING POWER
 REQUIREMENTS. A BUILDING COMPLIES WITH THIS SECTION IF
 ITS TOTAL CONNECTED LIGHTING POWER CALCULATED UNDER
 SECTION C405.5.1 IS NO GREATER THAN THE INTERIOR
 LIGHTING POWER CALCULATED UNDER SECTION C405.5.2.
 PROVIDE A LIGHTING POWER DENSITY CHART TO SHOW
 COMPLIANCE.
 6. SHEET E2.1- PLEASE SHOW COMPLIANCE WITH FBC EC
 405.7- A MINIMUM OF 50% OF ALL 125V, 15 AND 20AMP
 RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED WHERE
 INSTALLED IN PRIVATE OR OPEN OFFICES AND CLASSROOMS.
 THIS INCLUDES MODULAR PARTITIONS. SEE EXCEPTIONS IN
 CODE LANGUAGE.
 7. NEC 422.52 ELECTRIC DRINKING FOUNTAINS. ELECTRIC
 DRINKING FOUNTAINS SHALL BE PROTECTED WITH GROUND-FAULT
 CIRCUIT ?INTERRUPTER PROTECTION (GFI) AND BE READILY
 ACCESSIBLE. BREAKER AT PANELBOARD WILL SUFFICE, MARK
 PANELBOARD ACCORDINGLY.
 8. RISER DIAGRAM AND PANEL SCHEDULES, PLEASE PROVIDE
 AVAILABLE FAULT CURRENT AVAILABLE AT THE FPL SERVICE.
 ATTACH TO DOCUMENTS LETTER FROM FLORIDA POWER & LIGHT
 INDICATING AIC. SHOW AIC CALCULATION BASED ON
 INFORMATION PROVIDED BY UTILITY FOR APPROVAL. NEC
 110.24 FBC 107
 9. PROVIDE VOLTAGE DROP CALCULATIONS NOT ONLY FOR
 FEEDERS BUT ALSO THE BRANCH CIRCUIT FBC EC 505.7
 10. SHOW ON ONE-LINE PUMP STATION SEWAGE LIFT FROM MDP
 PANEL.
 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717