2016-09-09 15:13:36BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16080844
 ADD: 1101 54TH ST.
 CONT: ALBU & ASSOCIATES
 TEL: 407-788-1450
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. SEPT. 08/2016
 ACTION: DENIED
  
 1) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2) THE BUILDING PERMIT FOR THIS PROJECT INDICATES THE
 VALUE FOR THE PROJECT OF $2,643,849.00 DOLLARS. PLEASE
 NOTE THIS VALUE SHOULD ONLY REFLECT THE BUILDING, NOT
 ANY OF THE PERMIT VALUES FOR THE SITE IMPROVEMENT.
 THERE ARE (4) PERMITS THAT WILL COST $80.00 AN
 ADMINISTRATIVE FEE, (MECHANICAL, ELECTRICAL, PLUMBING &
 ROOFING) THESE VALUES SHOULD REMAIN IN THE BUILDING
 PERMIT. THE OTHER PERMITS TO BE REVIEWED UNDER SEPARATE
 PERMIT, WITH SEPARATE ASSOCIATED FEES ARE: FIRE
 SPRINKLER, FIRE ALARM, ALL LOW VOLTAGE PERMITS, KITCHEN
 EXHAUST HOODS, FIRE SUPPRESSION SYSTEMS, WALK IN
 COOLERS & FREEZERS, GREASE INTERCEPTORS?
  
 PERMITS THAT ARE NOT INCLUDED IN THE BUILDING PERMIT
 VALUE AND ARE SITE IMPROVEMENT PERMITS WOULD BE
 SITE CLEARING PERMITS, UNDERGROUND UTILITIES, LIFT
 STATIONS, PAVING AND DRAINAGE, STRIPPING OF PARKING
 LOTS, IRRIGATION, LANDSCAPE, SIGN PERMITS AWNINGS?
  
 3) SHEET LS1.0 UNDER THE HEADING CODE INFORMATION LIST
 THE WIND DESIGN TO ASCE 7-02. PLEASE REFER TO THE 2014
 FBC-B 1609.1.1 AND CHAPTER 35 THE REFERENCED STANDARDS
 ASCE 7-10.
  
 4) SHEET LS1.0 UNDER THE HEADING PROJECT USE A NEW
 CHEMICAL DEPENDENCY TREATMENT CENTER. THE OCCUPANCY
 TYPE A MIXED USE OF BUSINESS & I-1 ALCOHOL AND DRUG
 CENTERS). PLEASE BE AWARE IF THERE IS
 FOR MEDICAL CARE ON A 24-HOUR BASIS FOR MORE THAN FIVE
 PERSONS WHO ARE INCAPABLE OF SELF-PRESERVATION
 (DETOXIFICATION FACILITIES) THEN THE OCCUPANCY
 CLASSIFICATION WILL BE INSTITUTIONAL GROUP I-2. 2014
 FBC-B 308.4.
  
 5) PLEASE ALSO NOTE IF THIS PERMIT WERE RECLASSIFIED TO
 A GROUP I-2 OCCUPANCY THEN A BUILDING TYPE 5-B IS NOT
 ALLOWED. SEE FBC-B TABLE 503.
  
 6) SHEET LS1.0 IN THE UPPER LEFT HAND CORNER OF THE
 SHEET IS A HEADING, RATING AT 1-A SEPARATE FROM
 B-WING 1 HOUR CONSTRUCTION UNDERSIDE OF DECK. THERE ARE
 2 NOTES (1) THE CEILING SLEEPING WING TO BE DESIGNED TO
 UL LISTING P522 1 HOUR RATING. NOTE (2) THE INTERIOR
 SLEEPING ROOM CORRIDOR WALLS DESIGNED TO UL LISTING
 U419.
  
 PLEASE REFER TO SECTION 708.4 FBC-B EXCEPTION # 3. IT
 APPEARS YOU ARE TAKING THIS EXCEPTION BY NOT RUNNING
 THE 1 HOUR FIRE RATED CORRIDOR WALLS UP TO THE
 UNDERSIDE OF THE ROOF DECK. EXCEPTION # 3 WHERE THE
 CORRIDOR CEILING IS CONSTRUCTED AS REQUIRED FOR THE
 CORRIDOR WALLS, THE WALLS SHALL BE PERMITTED TO
 TERMINATE AT THE UPPER MEMBRANE OF SUCH CEILING
 ASSEMBLY.
  
 PLEASE SEE THE 2012 IBC BASE CODE COMMENTARY. EXCEPTION
 # 3 ALLOWS FOR A CORRIDOR TO BE CONSTRUCTED IN A TUNNEL
 FASHION- WITH RATED WALLS AND A RATED TOP. IN THESE
 CASES THE WALLS ARE NOT REQUIRED TO EXTEND TO THE
 UNDERSIDE OF A RATED ASSEMBLY. THIS IS A UNIQUE
 PROVISION IN THE CODE AND THE FACT THAT IT PERMITS A
 WALL ASSEMBLY TO BE TURNED INTO A HORIZONTAL POSITION
 SHOULD NOT BE APPLIED TO OTHER SECTIONS OF THE CODE OR
 OTHER RATED ASSEMBLIES. SEE FIGURE 708.4(2)( C ) FIRE
 PARTITION CONTINUITY.
  
 IN THIS CASE THE RATED WALL ASSEMBLY UL LISTING U419
 NEEDS TO BE TURNED ON ITS SIDE AND RATED DRYWALL ON
 EACH FACE OF THE HORIZONTAL ASSEMBLY.
  
 7) SHEET LS1.1 MISSING SCALE FOR THIS SHEET. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED.
  
 8) SHEET LS1.1 INDICATES THE BUILDING IS TO BE FIRE
 SPRINKLERED. THE BUILDING DOES NOT INDICATE IF THE FIRE
 SPRINKLER IS TO BE NFPA 13 FOR THE FULL BUILDING OR A
 PORTION THE INSTITUTIONAL DESIGNED TO BE A NFPA 13-R IN
 ACCORDANCE WITH 903.2.6 EXCEPTION 1 & 2. PLEASE NOTE IF
 THE FULL BUILDING IS NOT DESIGNED AS A FULL NFPA 13
 SYSTEM THEN THE AREA INCREASE FOR FIRE SPRINKLERS
 CANNOT BE TAKEN. FBC-B 506.3.
  
 9) SHEET A4.1 THE DOORS IDENTIFIED AS # 8 TO THE
 RESTROOMS 109 & 110 BOTH ARE SHOWN ON THE LIFE SAFETY
 SHEET IN A 1 HOUR FIRE RATED WALL BUT THE DOOR SCHEDULE
 ON A6.2 DOES NOT SHOW A FIRE RATED DOOR AND FRAME. 2014
 FBC-B TABLE 716.5.
  
 10) SHEET A4.1 VERSES S2.0 & S3.0 ON SHEET S2.0 NOTE #
 2 INDICATES THE USE OF AN INTERNAL MONOLITHIC FOOTING
 IN THE NORTH END OF THE BUILDING BUT THERE ARE NO WALL
 IDENTIFICATION TAGS INDICATING THESE WALLS ARE TO BE
 LOAD BEARING WALLS. THE WALL SCHEDULE SHOWS A WALL TYPE
 P4 AS A BEARING WALL. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 11) SHEET A4.2 VERSES S2.0 & S3.0 IN THE SOUTH END OF
 THE BUILDING ALSO INDICATES THE USE OF INTERNAL
 MONOLITHIC FOUNDATIONS. SHEET A4.2 ALSO SHOWS THE WALL
 TAG #7 FOR FIRE RATED WALLS. SHEET A6.1 IDENTIFIES THE
 P7 WALL AS UL LISTING U419 A NON-BEARING WALL? SHEET
 S3.0 DENOTES THIS AS A LOAD BEARING WALL, (362S162-33
 METAL/ 16 INCHES O. C.
  
 12) SHEET A4.2 AND SHEET LS1.1 DISCREPANCY IN PLANS,
 DOOR # 05 (CORRIDOR) HAS A 45 MIN. DOOR RATING SHEET
 LS1.1 AND A4.2, THE SAME DOOR IS IDENTIFIED AS # 5, THE
 DOOR SCHEDULE A6.2 INDICATES A 20 MIN. RATING,
 DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED. SEE TABLE 716.5 FBC-B.
  
 13) SHEET A4.2 AND SHEET LS1.1 DISCREPANCY IN PLANS,
 DOOR NUMBER 13 (NURSES BREAKROOM 147) HAS A 45 MIN.
 DOOR RATING SHEET LS1.1 AND A4.2, THE SAME DOOR IS
 IDENTIFIED A6.2 AS # 5, THE DOOR SCHEDULE INDICATES A
 20 MIN. RATING, DISCREPANCY IN PLANS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED. SEE TABLE 716.5
 FBC-B.
  
 14) SHEET A4.2 AND SHEET LS1.1 DISCREPANCY IN PLANS.
 THE ADA RESTROOM # 193, 196 BOTH HAVE WALL TAG
 IDENTIFYING THE WALL AS P10 A 6 INCH 30 MIN RATING ON
 SHEET A4.2 WHEREAS SHEET LS1.1 IS INDICATED AS A 1 HOUR
 WALL DISCREPANCY IN PLANS. NOTE 708.3 EXCEPTION # 1
 REFERS YOU TO TABLE 1018.1 WHEN REVIEWING BOTH
 FOOTNOTES B & C NO REDUCTION CAN BE TAKEN, 1 HOUR
 CORRIDOR WALL.
  
 15) SHEET A4.2 AND SHEET LS1.1 THE DOCTORS OFFICE
 CORRIDOR WALL TYPE IDENTIFIED AS P7 1 HOUR RATED U419
 ALSO HAS A WINDOW IDENTIFIED AS #7. SHEET A6.2 THE
 WINDOW SCHEDULE DOES NOT SHOW ANY COLUMN FOR FIRE RATED
 OPENINGS. PLEASE SHOW COMPLIANCE WITH SECTION TABLE
 716.6 OF THE FBC-B.
  
 16) SHEET A4.3 AND SHEET LS1.1. SHEET A4.3 ONLY HAS
 WALL IDENTIFICATION TAGS ON THE CORRIDOR WALLS. NONE OF
 THE OTHER WALLS WHICH LS1.1 SHOWS AS RATED WALLS ARE
 IDENTIFIED ON A4.3. PLEASE SHOW COMPLIANCE WITH SECTION
 708.1 OF THE FBC-B.
  
 17) SHEET S1.0 PROVIDES THE WIND DESIGN CRITERIA WITH
 AN EXPOSURE B. PLEASE REVIEW SECTION 1609.4.2 SURFACE
 ROUGHNESS C. OPEN TERRAIN WITH SCATTERED OBSTRUCTIONS
 HAVING HEIGHTS GENERALLY LESS THAN 30 FEET. THIS
 CATEGORY INCLUDES FLAT OPEN COUNTRY, AND GRASSLANDS.
 THIS SURFACE ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING
 LOCATED WITHIN SURFACE ROUGHNESS B TYPE TERRAIN WHERE
 THE BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY
 DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR
 D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET IN THE
 UPWIND DIRECTION AND A WIDTH GREATER THAN 150 FEET.
  
 18) THE WINDOW AND DOOR PRESSURES WILL INCREASE WITH
 THE C EXPOSURE WITH THE ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING. SEE TABLE 1609.7(2) FBC-B.
  
 19) PLEASE ALSO PROVIDE THE ROOF PRESSURES FOR ZONES 1,
 2, & 3. PLEASE PROVIDE THE PRESSURES IN THE VASD VALUES
 SINCE THE PRODUCT APPROVALS ARE IN VASD. PLEASE NOTE
 (2) ROOF CHARTS WILL BE REQUIRED, (1) FOR THE FLAT AREA
 OF THE ROOF AND A CHART FOR THE SLOPED ROOF 4:12. 2014
 FBC-B 1603.1.4 WIND DESIGN DATA.
  
 20A) PLEASE INDICATE IF EITHER THE CONTRACTOR OR THE
 DESIGNER OF RECORD WOULD PREFER TO DEFER THE PRODUCT
 APPROVALS UNTIL AFTER PERMIT ISSUANCE. 2014 FLORIDA
 BUILDING CODE W 2014 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS
 SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 20B) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31)
 SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT
 WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (F) SKYLIGHTS
 (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C
 STANDS
  
 20C) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 21) ROOF TOP A/C STANDS WILL REQUIRE A PRODUCT
 APPROVAL. EITHER THE CONTRACTOR OR THE DESIGNER OF
 RECORD WILL NEED TO COMPLETE THE FOLLOWING ON THE
 PRODUCT APPROVAL IN CALCULATING THE AREA OF THE ROOF
 TOP COMPRESSORS, THE MEAN ROOF HEIGHT OF THE STAND AND
 COMPRESSORS, WEIGHT, CIRCLED THE DESIGN PARAMETERS IN
 THE TABLES , ANCHORS AND UPLIFT VERSES MOMENT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 22) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 23) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  