| 2017-05-04 11:42:32 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION SECOND |
| | MECHANICAL REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | NOTE: |
| | MECHANICAL REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS THAT PERMIT MAY BE ISSUED AND CONTRACTOR MAY |
| | SUBMIT THE REQUIRED ITEMS AFTER THE PERMIT IS ISSUED |
| | BUT BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS. NOTE: |
| | REVISION FEES APPLY. CONTRACTOR TO RESPOND IN WRITING |
| | IF THE PROVISO OPTION IS PREFERRED AT THIS TIME. |
| | |
| | 1- PLANS DON'T SPECIFY IF A/C EQUIPMENT IS EXISTING OR |
| | NEW. IT DOESN'T SPECIFY SIZE OF EQUIPMENT. PROVIDE |
| | EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY SEC. |
| | R403.6 FBC-ENERGY CONSERVATION, 5TH EDITION (2014) TO |
| | VERIFY COMPLIANCE WITH THE ADDITIONAL LOAD. |
| | RESPONSE: PLANS ARE NOT CLEAR IF THE EXISTING A/C UNIT |
| | NEEDS TO BE UPDATED TO SERVE THE ADDITIONAL LOAD. |
| | CLEARLY SPECIFY ON PLANS IF THE A/C UNIT WAS UPDATED |
| | AND SPECIFY ON PLANS EQUIPMENT LISTED IN THE EQUIPMENT |
| | SIZING CALCULATIONS SUBMITTED. |
| | |
| | 2- A/C PLANS NEEDS TO SHOW COMPLIANCE WITH THE BALANCED |
| | RETURN AIR AS REQUIRED BY SEC. M1602.4 FBC-RESIDENTIAL, |
| | 5TH EDITION (2014). NOTE: TAKE INTO CONSIDERATION THAT |
| | NEED TO COUNT ALL THE SUPPLY AIR GOING TO THE MASTER |
| | BEDROOM, INCLUDING THE SUPPLY AIR TO THE UTILITY AREA |
| | AND BATHROOM. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |