| Date |
Text |
| 2017-05-04 07:50:26 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, SECOND |
| | BUILDING REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014) |
| | |
| | NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS THAT PERMIT MAY BE ISSUED AND CONTRACTOR MAY |
| | SUBMIT THE REQUIRED ITEMS AFTER THE PERMIT IS ISSUED |
| | BUT BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS. NOTE: |
| | REVISION FEES MAY APPLY. CONTRACTOR TO RESPOND IN |
| | WRITING IF THE PROVISO OPTION IS PREFERRED AT THIS |
| | TIME. PERMIT MAY BE PROCESSED ONCE THE ENERGY |
| | CALCULATIONS ARE SIGNED BY THE OWNER/AGENT, CONTRACTOR |
| | COMPLETES THE EPL FORM AND THE COUNTY IMPACT FEES STAMP |
| | AND PAID RECEIPT (IF REQUIRED) IS PROVIDED. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | RESPONSE: A) CONTRACTOR TO COMPLETE THE ENERGY |
| | PERFORMANCE LEVEL (EPL) CARD AS REQUIRED BY SEC. |
| | R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | B) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE |
| | BOTTOM OF THE ENERGY CALCULATIONS FORM SUBMITTED AS |
| | REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION, |
| | 5TH EDITION (2014). |
| | |
| | C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING THE BUILDER NAME. SEC. R101.5.1.1.2 |
| | FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | 2- INFORMATION SHOWN ON THE NEW "TYPICAL FRAMING AND |
| | CONNECTIONS @ OPENINGS" DETAIL DOESN'T MATCH |
| | INFORMATION SHOWN ON THE WALL SECTION 1/A. REVISE AS |
| | REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 3- INFORMATION SHOWN ON THE NEW "TYPICAL FRAMING AND |
| | CONNECTIONS @ OPENINGS" DETAIL IS NOT LEGIBLE. |
| | LETTERING IS TOO SMALL TO READ AND IS NO ADEQUATE FOR |
| | RECORDS RETENTION SCANNING. SEC. 107.2.1 AND SEC. |
| | 107.2.1.4 CITY AMENDMENTS. REVISE AS REQUIRED. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3 FOR: |
| | A) WINDOW MULLIONS AS SHOWN ON PLANS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | B) NOA 12-0809.04 SUBMITTED FOR HURRICANE SHUTTERS |
| | EXPIRED ON 04/18/2017. PROVIDE 2 COPIES OF CURRENT NOA. |
| | |
| | C) NEW MASTER BEDROOM EXTERIOR SWING DOOR. PROVIDE |
| | FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO |
| | DRAWINGS SUBMITTED. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | 5- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE |
| | PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY |
| | AMENDMENTS. |
| | |
| | 6- PROVIDE COMPLETE HURRICANE SHUTTERS INSTALLATION |
| | SCHEDULE (2 COPIES). SEE CITY SAMPLE. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | RESPONSE: REPEAT COMMENT. |
| | |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |