Plan Review Notes
Plan Review Notes For Permit 16080840
Permit Number 16080840
Review Stop B
Sequence Number 3
Notes
Date Text
2017-05-04 07:50:26RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, SECOND
 BUILDING REVIEW CHECKLIST.
 CODE: FBC 5TH EDITION (2014)
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS THAT PERMIT MAY BE ISSUED AND CONTRACTOR MAY
 SUBMIT THE REQUIRED ITEMS AFTER THE PERMIT IS ISSUED
 BUT BEFORE INSPECTIONS TO AVOID CONFLICTS/DELAYS. NOTE:
 REVISION FEES MAY APPLY. CONTRACTOR TO RESPOND IN
 WRITING IF THE PROVISO OPTION IS PREFERRED AT THIS
 TIME. PERMIT MAY BE PROCESSED ONCE THE ENERGY
 CALCULATIONS ARE SIGNED BY THE OWNER/AGENT, CONTRACTOR
 COMPLETES THE EPL FORM AND THE COUNTY IMPACT FEES STAMP
 AND PAID RECEIPT (IF REQUIRED) IS PROVIDED.
  
 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED
 BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
 RESPONSE: A) CONTRACTOR TO COMPLETE THE ENERGY
 PERFORMANCE LEVEL (EPL) CARD AS REQUIRED BY SEC.
 R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 B) OWNER OR LEGALLY DESIGNATED AGENT TO CERTIFY AT THE
 BOTTOM OF THE ENERGY CALCULATIONS FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 C) PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER NAME. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 2- INFORMATION SHOWN ON THE NEW "TYPICAL FRAMING AND
 CONNECTIONS @ OPENINGS" DETAIL DOESN'T MATCH
 INFORMATION SHOWN ON THE WALL SECTION 1/A. REVISE AS
 REQUIRED TO MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- INFORMATION SHOWN ON THE NEW "TYPICAL FRAMING AND
 CONNECTIONS @ OPENINGS" DETAIL IS NOT LEGIBLE.
 LETTERING IS TOO SMALL TO READ AND IS NO ADEQUATE FOR
 RECORDS RETENTION SCANNING. SEC. 107.2.1 AND SEC.
 107.2.1.4 CITY AMENDMENTS. REVISE AS REQUIRED.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3 FOR:
 A) WINDOW MULLIONS AS SHOWN ON PLANS.
 RESPONSE: REPEAT COMMENT.
  
 B) NOA 12-0809.04 SUBMITTED FOR HURRICANE SHUTTERS
 EXPIRED ON 04/18/2017. PROVIDE 2 COPIES OF CURRENT NOA.
  
 C) NEW MASTER BEDROOM EXTERIOR SWING DOOR. PROVIDE
 FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO
 DRAWINGS SUBMITTED.
 RESPONSE: REPEAT COMMENT.
  
 5- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 6- PROVIDE COMPLETE HURRICANE SHUTTERS INSTALLATION
 SCHEDULE (2 COPIES). SEE CITY SAMPLE. SEC. 107.2.1 CITY
 AMENDMENTS.
 RESPONSE: REPEAT COMMENT.
  
  
 ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH
 COMMENT TO EXPEDITE THE REVIEW PROCESS.
  