| Notes |
| Date |
Text |
| 2016-09-19 17:23:40 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION MECHANICAL | | | REVIEW COMMENTS. | | | CODE: FBC 5TH EDITION (2014). | | | | | | 1- PLANS DON'T SPECIFY IF A/C EQUIPMENT IS EXISTING OR | | | NEW. IT DOESN'T SPECIFY SIZE OF EQUIPMENT. PROVIDE | | | EQUIPMENT SIZING CALCULATIONS AS REQUIRED BY SEC. | | | R403.6 FBC-ENERGY CONSERVATION, 5TH EDITION (2014) TO | | | VERIFY COMPLIANCE WITH THE ADDITIONAL LOAD. | | | | | | 2- A/C PLANS NEEDS TO SHOW COMPLIANCE WITH THE BALANCED | | | RETURN AIR AS REQUIRED BY SEC. M1602.4 FBC-RESIDENTIAL, | | | 5TH EDITION (2014). NOTE: TAKE INTO CONSIDERATION THAT | | | NEED TO COUNT ALL THE SUPPLY AIR GOING TO THE MASTER | | | BEDROOM, INCLUDING THE SUPPLY AIR TO THE UTILITY AREA | | | AND BATHROOM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|