| 2016-09-15 08:54:57 | RESIDENTIAL (R3) CHANGE OF USE/ALTERATION, BUILDING |
| | REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION (2014) |
| | |
| | ***NOTE: |
| | CONTRACTOR NEEDS TO UPDATE THE LICENSE STATUS WITH THE |
| | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION |
| | (DBPR). |
| | |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD.) FOR IMPACT FEES ASSESSMENT. |
| | BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | NOTE: THIS MAY BE DONE LATER WHEN THE PERMIT IS READY |
| | TO BE PRINTED. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. R101.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION |
| | (2014). |
| | |
| | 3- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| | FOR THE NEW EXTERIOR DOOR AND WINDOWS. SEC. R301.1 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | 4- PROVIDE COMPLETE SPECIFICATIONS FOR THE WALL |
| | SHEATHING FASTENING AND EXTERIOR FINISH. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) WINDOW MULLIONS AS SHOWN ON PLANS. NOTE: CLEARLY |
| | SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE |
| | WITH THE CALCULATED DESIGN PRESSURES. SEC. R301.1 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | |
| | B) WINDOW PRODUCT APPROVAL NOA 14-0722.07 SUBMITTED IS |
| | FOR NON-IMPACT WINDOWS. THEREFORE NEED TO PROVIDE |
| | PRODUCT APPROVAL FOR HURRICANE SHUTTERS. AND PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. SEE CITY SAMPLE. |
| | |
| | C) NEW MASTER BEDROOM EXTERIOR SWING DOOR. PROVIDE |
| | FLORIDA PRODUCT APPROVAL COVER PAGE THAT CORRESPOND TO |
| | DRAWINGS SUBMITTED. |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR OR ENGINEER TO LIST THE CURRENT FLORIDA |
| | PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| | CONNECTOR. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ( NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |