| 2016-09-01 13:22:12 | ELECTRICAL REVIEW: |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: FPL MANATEE LAGOON ADDITIONAL ITEMS |
| | JOB ADDRESS: 6000 N. FLAGLER |
| | DESCRIPTION: ADD HANDICAP RAMP, HANDICAP PARKING AND |
| | SIDEWALKS. INSTALL CAR CHARGING STATION |
| | MASTER PERMIT: 16080793 |
| | |
| | AS DESCRIBED ABOVE, THE SCOPE OF THIS PERMIT INCLUDES |
| | THE INSTALLATION OF AN ELECTRIC VEHICLE CHARGING |
| | STATION WHICH IS FURTHER DESCRIBED ON SHEET C1.01 OF |
| | THE SUBMITTED PLANS. THE SUBMITTED PLANS REFER TO AN |
| | ELECTRICAL PAGE WHICH IS NOT INCLUDED IN THE PLAN SET. |
| | YOU WILL NEED TO PROVIDE THE FOLLOWING FOR A SUCCESSFUL |
| | ELECTRICAL REVIEW: |
| | |
| | 1. PROVED AN ELECTRICAL SITE PLAN INDICATING THE |
| | LOCATION OF THE PROPOSED CHARGING STATION AND THE |
| | LOCATION OF THE POWER SOURCE FOR SAME. |
| | 2. PROVIDE SPECS ON THE PROPOSED CHARGER TO DETERMINE |
| | THE DEMAND LOAD FOR THE EQUIPMENT. |
| | 3. SUBMIT A RISER DIAGRAM INCLUDING LOAD CALCS TO |
| | ASCERTAIN THAT THE EXISTING SERVICE IS CAPABLE OF |
| | ACCEPTING THE ADDED LOAD. |
| | 4. CONSIDER ALL THE REQUIREMENTS SET FORTH IN ARTICLE |
| | 625 OF THE 2011 EDITION OF THE NEC |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |