| 2016-11-10 11:41:30 | 1) PROVIDE THE BTU LOAD FOR EACH GAS APPLIANCE. I | | | CANNOT DO A REVIEW WITHOUT THE BTU LOAD OF EACH | | | APPLIANCE. THE ORIGINAL GAS DRAWING THAT HAS BEEN | | | SUBMITTED IS SO SMALL IN SIZE IT IS ILLEGIBLE. | | | | | | 2.) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2014 | | | FBC-FUEL GAS CODE SEC.304.1 OR 2014 FBC-RES. SEC. G | | | 2407. | | | | | | 3) SUBMIT COPIES OF THE SIZING TABLES YOU ARE USING FOR | | | THE PE PIPE AND THE CSST OR REFERENCE THE SPECIFIC | | | SIZING TABLES THAT ARE BEING USED ON THE PLANS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|