Notes
Date Text
2016-08-18 13:09:55REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1) SHOW LOCATION OF GFCI RECEPTACLE OUTLETS IN THE
 KITCHEN COUNTER-TOP SPACE AND VERIFY 2 SMALL APPLIANCE
 CIRCUITS ARE EXISTING. FBC-R SECTIONS E3703.2 &
 E3901.2.4
  
 2) SHOW LOCATION OF GFCI RECEPTACLE OUTLET WITHIN 3' OF
 THE BATHROOM SINK AND VERIFY IF A 20 AMP CIRCUIT IS
 EXISTING. FBC-R SECTIONS E3703.4 & E3901.7
  
 3) SMOKE ALARMS REQUIRED PER FBC-R 314 & 315. IF
 EXISTING PLEASE MAKE A NOTE.
  
 4) ELECTRICAL SUB-PERMIT IS REQUIRED [ GENERAL
 INFORMATIONAL NOTE ]