Plan Review Notes
Plan Review Notes For Permit 16080719
Permit Number 16080719
Review Stop R
Sequence Number 1
Notes
Date Text
2016-09-15 08:01:581- CLARIFY WHY SUBMITTING NOA 12-0426.06 FOR ROOF
 COATING SYSTEMS. THIS PRODUCT MAY NO BE SUITABLE FOR
 THE EXISTING ROOF SYSTEM. SEE LIMITATIONS ON LAST PAGE
 OF NOA SUBMITTED. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR:
 A) ROOF UNDERLAYMENT: NOA 11-1011.05 SUBMITTED EXPIRED
 ON 03/03/15. PROVIDE CURRENT NOA.
  
 B) ROOFING TILES: FLORIDA PRODUCT APPROVAL FL7473-R5
 SUBMITTED IS FOR THE 2010 FBC. NEED TO PROVIDE PRODUCT
 APPROVAL FOR THE CURRENT 2014 CODE.
  
 3- DESIGNER OF RECORD TO REVIEW/APPROVE ALL PRODUCT
 APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS. NOTE: PLEASE PLACE THE REVIEW STAMP ON THE
 FRONT OF THE PRODUCT APPROVAL NOT ON THE BACK OF THE
 FRONT PAGE. THIS IS REQUIRED FOR PROPER SCANNING OF
 DOCUMENTS FOR RECORDS RETENTION AS REQUIRED BY SEC.
 107.2.1.4 CITY AMENDMENTS.
  