| Plan Review Notes For Permit 16080719 |
| Permit Number |
16080719 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-22 13:51:14 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PROVIDE EXISTING ELECTRIC SERVICE RISER WITH WIRE | | | SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. COMPLETE | | | LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW CIRCUITS ON | | | FLOOR PLAN.FBC- 107.3.5.3 | | | | | | 2] ALL NEWLY INSTALLED RECEPTACLES SHALL BE TAMPER | | | RESISTANT PER FBC-R SECTION E4002.14 | | | | | | 3] ALL NEWLY INSTALLED LUMINAIRES SHALL BE 75 % HIGH | | | EFFICIENT AND IC RATED SEALED TO NOT COMPROMISE | | | BUILDING THERMAL ENVELOPE IN ACCORDANCE WITH FBC-E | | | SECTIONS 402.4.4 & 404.1 |
|