Notes
Date Text
2016-08-18 14:58:39REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] ELECTRICAL SUB-PERMIT REQUIRED. PROVIDE AN EXISTING
 RISER-DIAGRAM AND PANEL SCHEDULE WITH LOAD CALCS. FBC
 107.3.5.3
  
 2] SHOW LOCATIONS OF GFCI RECEPTACLE OUTLETS ON THE
 KITCHEN COUNTER-TOP. NEC 210.52(C)
  
 3] SHOW LOCATIONS OF GFCI RECEPTACLE OUTLETS WITHIN 3'
 OF THE BATHROOM SINK. NEC 210.52(D)
  
 4] SMOKE ALARMS REQUIRED PER FBC-R 314 & 315. IF
 EXISTING PLEASE MAKE A NOTE.