| Plan Review Notes For Permit 16080693 |
| Permit Number |
16080693 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-18 14:58:39 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] ELECTRICAL SUB-PERMIT REQUIRED. PROVIDE AN EXISTING | | | RISER-DIAGRAM AND PANEL SCHEDULE WITH LOAD CALCS. FBC | | | 107.3.5.3 | | | | | | 2] SHOW LOCATIONS OF GFCI RECEPTACLE OUTLETS ON THE | | | KITCHEN COUNTER-TOP. NEC 210.52(C) | | | | | | 3] SHOW LOCATIONS OF GFCI RECEPTACLE OUTLETS WITHIN 3' | | | OF THE BATHROOM SINK. NEC 210.52(D) | | | | | | 4] SMOKE ALARMS REQUIRED PER FBC-R 314 & 315. IF | | | EXISTING PLEASE MAKE A NOTE. |
|