| 2016-09-12 09:31:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. THE BASE SHEET FASTENING FOR THE JOHNS MANVILLE | | | MODIFIED DOES NOT APPEAR TO BE CORRECT, FBC 1609. SEE | | | PERIMETER AND CORNER FASTENING; IT APPEARS THAT THE | | | PERIMETER REQUIRES 4" FASTENING FOR 3 FIELD ROWS, | | | CORNER ZONES REQUIRE 5". (IT APPEARS THAT THE WRONG | | | COLUMN WAS UTILIZED WHEN SPECIFYING FASTENING; | | | CALCULATIONS APPEAR CORRECT.) | | | | | | 2. WHEN RESUBMITTING, PLEASE COLLATE THREE IDENTICAL | | | COMPLETE SETS FOR PERMIT ISSUANCE. | | | | | | |
|