| Plan Review Notes For Permit 16080670 |
| Permit Number |
16080670 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-18 18:47:54 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | | | | 1] CLARIFY HOW ALL UNGROUNDED AND GROUNDED FEEDER | | | CONDUCTORS WILL FIT IN A 1/2'' CONDUIT ? PLEASE LOOK AT | | | CONDUIT FILL TABLES AND ANNEXES.( # 6 AWG, 10 AWG ) | | | | | | 2] PROVIDE HEATER MANUFACTURE SPECS (GAS OR ELECTRIC) ? | | | OTHERWISE IN ORDER TO VERIFY POOL PANEL IS ADEQUATE TO | | | HANDLE LOADS PROVIDE EXISTING LOAD CALCS. FBC 107 | | | | | | 3] ALL POOL HEATERS SHALL BE EQUIPPED WITH ON-OFF | | | CONTROL AND A TIME SWITCH PER FBC-E SECTION R4039.1 & | | | R4039.2 |
|