2016-08-18 18:47:54REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
  
 1] CLARIFY HOW ALL UNGROUNDED AND GROUNDED FEEDER
 CONDUCTORS WILL FIT IN A 1/2'' CONDUIT ? PLEASE LOOK AT
 CONDUIT FILL TABLES AND ANNEXES.( # 6 AWG, 10 AWG )
  
 2] PROVIDE HEATER MANUFACTURE SPECS (GAS OR ELECTRIC) ?
 OTHERWISE IN ORDER TO VERIFY POOL PANEL IS ADEQUATE TO
 HANDLE LOADS PROVIDE EXISTING LOAD CALCS. FBC 107
  
 3] ALL POOL HEATERS SHALL BE EQUIPPED WITH ON-OFF
 CONTROL AND A TIME SWITCH PER FBC-E SECTION R4039.1 &
 R4039.2