| 2016-09-07 17:02:16 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, | | | ENERGY CONSERVATION CODES | | | PERMIT #16080659 | | | 9/7/16 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS IN | | | ACCORDANCE WITH SECTUION C403.2.1 FBC-14 ENERGY | | | CONSERVATION. THE SUMMARY CALCULATION ON SHEET M-1 IS | | | INCOMPLETE. | | | | | | 2) PROVIDE AN EQUIPMENT SCHEDULE FOR THE VAV BOXES, AND | | | TYPICAL BOX INSTALLATION DETAILS. | | | | | | 3) THE RTU, CONDENSER, AND ROOFTOP FAN EQUIPMENT | | | MOUNTING DETAILS ARE INCOMPLETE. PLEASE PROVIDE THE | | | WIND LOAD DESIGN CRITERIA AND COMPLETE ANCHORING AND | | | FASTENING DETAILS- SECTION 301.15. SUBMIT A FL. PRODUCT | | | APPROVAL OR MIAMI-DADE NOA FOR THE ROOF STAND. | | | | | | 4) PROVIDE A CONDENSATE DISPOSAL PLAN. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|