| Date |
Text |
| 2016-10-13 09:46:51 | 1) THE DESIGN PROFESSIONAL IS REQUIRED TO DESIGNATE TO |
| | WHICH DESIGN SPECIFICATION ( A OR B) OF THE FAIR |
| | HOUSING ACT THE UNIT BATHROOMS WERE DESIGNED. 2ND |
| | REQUEST |
| | IF SPECIFICATION A IS SELECTED AS THE BASIS FOR |
| | DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING |
| | UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF |
| | SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE |
| | DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER |
| | BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE |
| | ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING. |
| | 2A) SHEET A3.22 - UNIT B3 - SHOWS A DWELLING UNIT WITH |
| | 2 BEDROOMS AND 2 BATHROOMS, ONE HAS A TUB THE OTHER A |
| | SHOWER. THE DESIGN PROFESSIONAL IS REQUIRED TO |
| | DESIGNATE TO WHICH DESIGN SPECIFICATION OF THE FAIR |
| | HOUSING ACT (A OR B) THE UNIT BATHROOMS WERE DESIGNED. |
| | IF SPECIFICATION A IS SELECTED AS THE BASIS FOR |
| | DESIGNING A BATHROOM, ALL BATHROOMS IN THE DWELLING |
| | UNIT ALSO MUST COMPLY WITH THE A SPECIFICATION. IF |
| | SPECIFICATION B IS SELECTED, ONLY ONE BATHROOM IN THE |
| | DWELLING UNIT MUST MEET THOSE REQUIREMENTS: ALL OTHER |
| | BATHROOMS IN THE DWELLING UNIT MUST BE ON AN ACCESSIBLE |
| | ROUTE, DOORS HAVING A 32-INCH CLEAR OPENING. |
| | 3) SHT. A-3.10 & A-.21 - WATER SUPPLY VALVES FOR THE |
| | STACKED WASHER/DRYER UNIT SHALL BE ACCESSIBLE PER 2010 |
| | FPC SEC.606.3. NOTE THIS ON THE PLAN.2ND REQUEST. |
| | 4) SHT. A-3.41 - SHOW THE LENGTH AND WIDTH DIMENSIONS |
| | OF THE ACCESSIBLE TOILET ROOMS ON DETAILS #3 & #4. 2ND |
| | REQUEST. |
| | 5)WHEN SUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |