Plan Review Notes
Plan Review Notes For Permit 16080655
Permit Number 16080655
Review Stop B
Sequence Number 1
Notes
Date Text
2016-08-17 11:18:14PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 SECTIONS G & H - TECTUM DECK
  
 1) SPECIFY THE APPROVED ASSEMBLY AND ITS MAXIMUM DESIGN
 PRESSURE FROM THE ONES THAT ARE LISTED IN NOA NO.
 14-0626.04 THAT WILL BE USED. FBC 107.2.1
 NOTE: THE NOA REFERS TO RAS 117 FOR INSULATION
 ATTACHMENT. RAS 117 SECTION 12.6.1 BONDED ROOF
 ASSEMBLIES MAY BE TESTED IN ACCORDANCE WITH TAS 124 TO
 VERIFY ATTACHMENT IN THE ELEVATED PRESSURE ZONES.
  
 SECTIONS C, D, E, F & H - STEEL DECK
  
 1) SPECIFY WHICH ONE OF THE FASTENING OPTIONS ON PAGE
 16 OF NOA NO.14-0626.02 WILL BE USED. FBC 107.2.1
  
 2) SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 AND/OR
 RAS 137 CALCULATIONS FOR ENHANCED FASTENING IN THE
 PERIMETER AND CORNER AREAS AS REQUIRED BY LIMITATION
 NUMBER 7 ON PAGE 24 OF NOA NO.14-0626.02.
  
 3) SUBMIT TWO SETS OF FIELD WITHDRAWAL TESTING AND
 SIGNED & SEALED CALCULATIONS AS REQUIRED BY STEEL DECK
 LIMITATIONS NUMBER 1 ON PAGE 23 OF NOA NO.14-0626.02.
 ALL TESTING AND FASTENING DESIGN SHALL BE IN COMPLIANCE
 WITH TAS 105 AND RAS 137.
  
  
  