| Plan Review Notes For Permit 16080618 |
| Permit Number |
16080618 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-14 07:08:38 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080618 | | | 10/14/16 | | | | | | 1) SHEET M2.1: INDICATE THE TYPES AND SIZES OF THE MAIN | | | SUPPLY AND RELOCATED BRANCH DUCTS SUPPLYING THE | | | RELOCATED VAV BOXES. | | | | | | 2) M2.1: INDICATE THE FLEX DUCT SIZES OR RELOCATE THE | | | FLEX DUCT SCHEDULE FROM M6.1. | | | | | | 3) NUMBER THE VAV BOXES AND PROVIDE AN EQUIPMENT | | | SCHEDULE LISTING MAKES AND MODELS, AND COOLING, | | | HEATING, AND CFM CAPACITIES. | | | | | | 4) PROVIDE A DETAIL FOR INSTALLATION OF THE RELOCATED | | | VAV BOXES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|