| Plan Review Notes For Permit 16080618 |
| Permit Number |
16080618 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-24 08:19:17 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, | | | ENERGY CONSERVATION CODES | | | PERMIT #16080618 | | | 8/24/16 | | | | | | 1) SUBMIT AC LOAD CALCULATIONS FOR THE NEW AC SYSTEMS- | | | SECTION C403.2.1 FBC-14 ENERGY CONSERVATION, | | | | | | 2) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 3) PROVIDE A MECHANICAL ROOF PLAN SHOWING THE LOCATIONS | | | OF THE NEW AC CONDENSERS. | | | | | | 4) PROVIDE WIND LOAD ENGINEERING FOR ATTACHMENT OF THE | | | CONDENSERS AND STANDS TO THE ROOF STRUCTURE- SECTION | | | 301.15. SUBMIT NOA # 13-1017.09 WITH REVIEW SIGNATURE | | | BY THE EOR. | | | | | | 5) PROVIDE INSTALLATION DETAILS FOR THE NEW AHU'S AND | | | MMU. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|