| 2016-08-25 12:44:24 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE |
| | WILL SUFFICE. |
| | 2. AT THE LEAST 50% OF ALL 125-VOLT, 15- AND 20-AMPERE |
| | RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED WHERE |
| | INSTALLED IN PRIVATE OFFICES, OPEN OFFICES, AND |
| | COMPUTER CLASSROOMS. THIS INCLUDES THOSE INSTALLED IN |
| | MODULAR PARTITIONS. THERE ARE THREE ACCEPTABLE METHODS |
| | FOR CONTROLLING THE RECEPTACLES: A SCHEDULED |
| | TIME-OF-DAY CONTROL DEVICE THAT TURNS THE RECEPTACLES |
| | OFF AT SPECIFIC PROGRAMMED TIMES. A SEPARATE PROGRAMMED |
| | SCHEDULE IS REQUIRED FOR EACH FLOOR AND CANNOT EXCEED |
| | 25,000 SQ.FT OF AREA. AN OCCUPANT SENSOR THAT TURNS THE |
| | RECEPTACLES OFF WITHIN 30-MINUTES OF ALL OCCUPANTS |
| | LEAVING A SPACE. A SIGNAL FROM ANOTHER CONTROL OR ALARM |
| | SYSTEM THAT INDICATES THE AREA IS NOT OCCUPIED AND |
| | FUNCTIONS TO TURN THE RECEPTACLES OFF. THERE ARE (2) |
| | EXCEPTIONS: RECEPTACLES SPECIFICALLY DESIGNATED FOR |
| | EQUIPMENT REQUIRING 24-HOUR OPERATION, AS DETERMINED BY |
| | THE AHJ. SPACES WHERE AN AUTOMATIC SHUTOFF WOULD |
| | ENDANGER THE SAFETY OR SECURITY OF THE ROOM OR BUILDING |
| | OCCUPANT(S), AS DETERMINED BY THE AHJ. SHOW COMPLIANCE. |
| | 3. SHOW A RECEPTACLE AT THE A/C LOCATED ON ROOFTOOP TO |
| | BE WP/GFCI PROTECTED, AND ON PANEL SCHEDULE. NEC 210.63 |
| | 4. PROVIDE A NOTE TO COMPLY WITH NEC 450.13B HOLLOW |
| | SPACE INSTALLATION OF TRANSFORMER. PLEASE CLARIFY IF |
| | PANEL A IS IN RATED WALL CORRIDOR. PROVIDE NOTE TO |
| | MAINTAIN FIRE RATINGS. |
| | 5. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE |
| | TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS REGARDING |
| | THIS PROJECT. |
| | |
| | |