| Plan Review Notes For Permit 16080576 |
| Permit Number |
16080576 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-01 10:25:37 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. LABE THEL P-TRAP LOCATED DOWN STEAM OF MASTER | | | BATHROOM ON RISER DIAGRAM. PER WPB AMEND TO FBC 107.2.1 | | | | | | 2. KITCHEN SINK IS NOT VENTED IT SHALL COMPLY WITH FBC | | | PL P3101.2.1 VENTING REQUIRED. | | | EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN | | | ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN | | | THIS CHAPTER. | | | | | | 3. A CLEANOUT IS REQUIRED WHERE THE 4IN BRANCH FOR KIT | | | , LAUNDRY EXITS BUILDING BEFORE IT CONNECTS TO | | | SEWER.PER FBC PL P3005.2.7 | | | | | | 4. A TRAP PRIMER IS REQUIRED ON ALL FLOOR DRAINS. PER | | | FBC PL P3201.2 TRAP SEALS AND TRAP SEAL PROTECTION. | | | TRAPS SHALL HAVE A LIQUID SEAL NOT LESS THAN 2 INCHES | | | (51 MM) AND NOT MORE THAN 4 INCHES (102 MM). TRAPS FOR | | | FLOOR DRAINS SHALL BE FITTED WITH A TRAP PRIMER OR | | | SHALL BE OF THE DEEP SEAL DESIGN. TRAP SEAL PRIMER | | | VALVES SHALL CONNECT TO THE TRAP AT A POINT ABOVE THE | | | LEVEL OF THE TRAP SEAL. |
|