| 2016-08-17 10:25:25 | JOB PERMIT NUMBER: 16080576 |
| | JOB ADDRESS: 925 39TH COURT |
| | WEST PALM BEACH FLORIDA |
| | DATE: AUGUST 17, 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | 1) SMOKE ALARMS REQUIRED IN EACH SLEEPING ROOM, OUTSIDE |
| | OF EACH SLEEPING AREA, AND ON ANY ADDITIONAL HABITABLE |
| | STORY OF A DWELLING. REFLECT LOCATION ON PLANS, THEY |
| | SHALL BE INTERCONNECTED AND PROTECTED BY AN ARC-FAULT |
| | BKR UNLESS EXCEPTIONS APPLY. FBC-R314 |
| | 2) CARBON MONOXIDE ALARMS REQUIRED WITHIN 10' OF EACH |
| | SLEEPING ROOM WHERE A FOSSIL FUEL APPLIANCE, FIREPLACE, |
| | OR AN ATTACHED GARAGE IS PRESENT. REFLECT LOCATION ON |
| | PLANS, THEY SHALL BE INTERCONNECTED AND PROTECTED BY AN |
| | ARC-FAULT BKR UNLESS EXCEPTIONS APPLY. FBC-R315 |
| | 3) SHEET E-1.0, IF ON THE MASTER BATH 2 SEPARATE OR A |
| | DOUBLE SINK IS GONA BE USED ADD A 20 AMP GFCI OUTLET |
| | WITHIN 3' OF THE BASIN EDGE AS PER FBC-R SECTION |
| | E3901.6 |
| | 4) SHEET E-1.0, INSTALL A 20 AMP GFCI OUTLET WITHIN |
| | 12'' OF THE TOP OF THE COUNTER-TOP ON THE KITCHEN |
| | ISLAND. FBC-R SECTION E3901.4.2 |
| | 5) SHEET E-1.0, GARAGE DOOR OPENER OUTLET NOT SHOWN, |
| | KEEP IN MIND THE RECEPTACLE SHALL BE GFCI PROTECTED PER |
| | FBC-R SECTION E3902.2 |
| | 6) SHEET E-1.0, ADD A GFCI OUTLET IN THE FRONT AND BACK |
| | OF THE HOUSE, PLUS THE OUTSIDE LOGGIA REQUIRES 1 |
| | RECEPTACLE ACCESSIBLE WITHIN 6.5' FROM GRADE. FBC-R |
| | SECTION E3901.7 |
| | 7) SHEET E-1.0, LAUNDRY ROOM DOESN'T SHOW LOCATION OF |
| | WASHER AND DRYER OUTLETS. KEEP IN MIND ANY ADDITIONAL |
| | RECEPTACLE WITHIN THE LAUNDRY ROOM SHALL BE GFCI |
| | PROTECTED. FBC-107 MINIMUM PLAN REVIEW |
| | 8) PROVIDE LOCATION OF THE NEW 200 AMP PANEL ''A'' ON |
| | THE FLOOR PLAN TO VERIFY WORKING CLEARANCE AND A PANEL |
| | SCHEDULE WITH MATCHING CIRCUITS. FBC-107 MINIMUM PLAN |
| | REVIEW. |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. WHEN RESUBMITTING, FOR A |
| | QUICKER RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED |
| | TO PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING |
| | EACH ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL |
| | FORM. |
| | THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER'S |
| | COMMENTS AND YOUR RESPONSE OR ACTION TO SAME. |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON'T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |
| | MARIO VALDES |
| | ELECTRICAL PLAN EXAMINER |