Plan Review Notes
Plan Review Notes For Permit 16080567
Permit Number 16080567
Review Stop E
Sequence Number 2
Notes
Date Text
2016-09-22 14:04:262ND ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC) & NFPA 72
  
 PROJECT NAME: A PARADISE ALF
 JOB ADDRESS: 438 MACY STREET
 DESCRIPTION: INSTALL A MONITORED FIRE ALARM PER
 ATTACHED PLANS
 MASTER PERMIT: 16080567
  
 BEFORE YOU CAN PROPERLY DESIGN THE FIRE ALARM SYSTEM
 FOR THESE PREMISES, A CHANGE OF OCCUPANCY PERMIT IS
 REQUIRED. THIS WILL DETERMINE THE FIRE ALARM SYSTEM
 REQUIRED. NEVER THE LESS, BELOW PLEASE FIND A LIST OF
 REQUIRED CORRECTIONS REQUIRED WITH THE PLANS AS
 SUBMITTED. ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER
 REVIEW OF SUBMITTED CORRECTIONS.
  
 THE PREMISES ARE AT THIS POINT CLASSIFIED SINGLE
 FAMILY. A CHANGE OF OCCUPANCY/USE PERMIT IS REQUIRED
 AND THERE IS WHERE THE TYPE AND LOAD OF OCCUPANCY WILL
 BE DETAILED.
  
 1. YOU NEED TO SHOW PROOF OF VALUATION BY PROVIDING A
 COPY OF THE ACCEPTED CONTRACT.
 DECLARED VALUATION ON THE PERMIT APPLICATION WAS RAISED
 TO $4664.15, THE TOTAL COST OF THE JOB.
  
 2. INDICATE ON THE PLANS OR LEGEND THE NUMBER OF
 DEVICE.
 SATISFIED.
  
 3. PROVIDE A UL CERTIFICATE FOR THE CENTRAL STATION.
 SATISFIED.
  
 4. PROVIDE ON THE PLANS THE SEQUENCE OF OPERATION.
 SATISFIED.
  
 5. PROVIDE THE OCCUPANT LOAD FOR EACH ROOM.
 AS INDICATED ABOVE, THE OCCUPANT LOAD WILL BE DETAILED
 ON THE CHANGE OF OCCUPANCY/USE PERMIT ONCE APPROVED.
 6. MAKE CERTAIN THAT ALL PULL STATION ARE WITHIN 5? OF
 THE DOORWAY.
 P1- MANUAL PULL STATION DOES NOT APPEAR TO BE WITHIN
 THE REQUIRED DISTANCE. RELOCATE ALONGSIDE OF THE DOOR.
  
 7. INDICATE ON THE PLANS THE CANDELA RATING OF EACH
 STROBE DEVICE.
 SATISFIED.
  
 8. THE RISER DIAGRAM AS DRAWN ON THE PLANS APPEARS TO
 HAVE MORE IDCS THAN INDICATED ON THE PANEL SPECS.
 SATISFIED.
  
 9. RISER DIAGRAM AND DEVICE LEGEND INDICATE DIFFERENT
 FACP, CORRECT ACCORDINGLY.
 MARK ON THE PLANS THE LOCATION OF THE FACP, FAAP &
 ELECTRICAL PANEL FOR LOCATION OF POWER SOURCE.
  
 10. ZONE 5 ON THE FLOOR PLAN AND RISER DO NOT MATCH.
 CORRECT ACCORDINGLY.
 SATISFIED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE?SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE?SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER