| Date |
Text |
| 2016-08-16 17:34:21 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: A PARADISE ALF |
| | JOB ADDRESS: 438 MACY STREET |
| | DESCRIPTION: INSTALL A MONITORED FIRE ALARM PER |
| | ATTACHED PLANS |
| | MASTER PERMIT: 16080567 |
| | |
| | BEFORE YOU CAN PROPERLY DESIGN THE FIRE ALARM SYSTEM |
| | FOR THESE PREMISES, A CHANGE OF OCCUPANCY PERMIT IS |
| | REQUIRED. THIS WILL DETERMINE THE FIRE ALARM SYSTEM |
| | REQUIRED. NEVER THE LESS, BELOW PLEASE FIND A LIST OF |
| | REQUIRED CORRECTIONS REQUIRED WITH THE PLANS AS |
| | SUBMITTED. ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER |
| | REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. YOU NEED TO SHOW PROOF OF VALUATION BY PROVIDING A |
| | COPY OF THE ACCEPTED CONTRACT. |
| | 2. INDICATE ON THE PLANS OR LEGEND THE NUMBER OF |
| | DEVICE. |
| | 3. PROVIDE A UL CERTIFICATE FOR THE CENTRAL STATION. |
| | 4. PROVIDE ON THE PLANS THE SEQUENCE OF OPERATION. |
| | 5. PROVIDE THE OCCUPANT LOAD FOR EACH ROOM. |
| | 6. MAKE CERTAIN THAT ALL PULL STATION ARE WITHIN 5? OF |
| | THE DOORWAY. |
| | 7. INDICATE ON THE PLANS THE CANDELA RATING OF EACH |
| | STROBE DEVICE. |
| | 8. THE RISER DIAGRAM AS DRAWN ON THE PLANS APPEARS TO |
| | HAVE MORE IDC?S THAT INDICATED ON THE PANEL SPECS. |
| | 9. RISER DIAGRAM AND DEVICE LEGEND INDICATE DIFFERENT |
| | FACP, CORRECT ACCORDINGLY. |
| | 10. ZONE 5 ON THE FLOOR PLAN AND RISER DO NOT MATCH. |
| | CORRECT ACCORDINGLY. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |