Plan Review Notes
Plan Review Notes For Permit 16080560
Permit Number 16080560
Review Stop E
Sequence Number 2
Notes
Date Text
2016-10-24 14:21:342ND REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - APPLICANT HAS NOT ADDRESSED INTIAL PLAN REVIEW
 COMMENTS. IF ANY QUESTIONS PLEASE CALL OR EMAIL.
  
 1] FBC-E SEC C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS.
  
 2] THE STATED VALUATION OF $1,100.00 IS TOO LOW FOR THE
 INSTALLATION OF PROPOSED SIGNAGE. THE PERMIT VALUATION
 AND PERMIT FEE MUST BE EQUIVALENT WITH THE VALUATION
 AND FEE THAT A LICENSED CONTRACTOR WOULD PROVIDE.
 PLEASE INCREASE THE VALUATION ACCORDINGLY. FBC-109.3