2016-08-18 19:21:57REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 1] FBC-E SECTION C405.2.4 EXTERIOR LIGHTING CONTROLS.
 LIGHTING NOT DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY EITHER A COMBINATION OF A
 PHOTOSENSOR AND A TIME SWITCH, OR AN ASTRONOMICAL TIME
 SWITCH. LIGHTING DESIGNATED FOR DUSK-TO-DAWN OPERATION
 SHALL BE CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR.
 ALL TIME SWITCHES SHALL BE CAPABLE OF RETAINING
 PROGRAMMING AND THE TIME SETTING DURING LOSS OF POWER
 FOR A PERIOD OF AT LEAST 10 HOURS. ( A NOTE WILL
 SUFFICE )
  
 2] COMPLY WITH BUILDING COMMENTS FOR PERMIT AND JOB
 COST EVALUATION.