| Plan Review Notes For Permit 16080550 |
| Permit Number |
16080550 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-09-29 07:35:09 | 2ND REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080550 | | | 9/29/16 | | | | | | 1) 2ND REQUEST FOR MECHANICAL PLANS AND VENTILATION | | | CALCULATIONS- SEE 1ST REVIEW COMMENT PRINTED BELOW: | | | | | | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES | | | PERMIT #16080550 | | | 8/23/16 | | | | | | 1) THE PLANS INDICATE A LEVEL 2 ALTERATION PER SECTION | | | 504.1 FBC-14 EXISTING BUILDING CODE. PLEASE PROVIDE | | | MECHANICAL ALTERATION PLANS, AND MINIMUM VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES- SEE SECTION | | | 809.1 FBC-14 EXISTING BUILDING, AND TABLE 403.3 FBC-14 | | | MECHANICAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|