| Plan Review Notes For Permit 16080548 |
| Permit Number |
16080548 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-10 06:52:59 | 1) SHT. 077-A2.0 - DETAIL #5 - THE CAFE COUNTER SHALL | | | BE A MAXIMUM OF 34 INCHES ABOVE THE FINISH FLOOR. FL. | | | ACCESS CODE ACC. SEC. 212, 606. | | | 2)SHT. 077 - A2.0 - DETAIL #4 - THE 3 COMPARTMENT SINK | | | SHOWN IN THE MEN'S RESTROOM SHALL COMPLY WITH FAC | | | SEC.212.3, 213.3.4. | | | 3) A SAMPLING PORT IS REQUIRED ON THE DISCHARGE OUTLET | | | OF THE OIL SEPARATOR FOR THE UTILITIES DEPT. TO SAMPLE | | | THE EFFLUENT. | | | 4) SHT.203 - P2.1 - FLAT DRY VENTS ARE SHOWN ON THE OIL | | | SEPARATOR. THE VENTS SHALL CONNECT ABOVE THE CENTERLINE | | | OF THE DRAIN PIPE PER THE FPC SEC.905.3. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|