Plan Review Notes
Plan Review Notes For Permit 16080543
Permit Number 16080543
Review Stop M
Sequence Number 3
Notes
Date Text
2016-12-29 16:25:253RD REVIEW FBC-2014 MECHANICAL
 PERMIT #16080543
 12/28/16
  
 1) SHEET M-1: PLEASE CLEARLY IDENTIFY THE SMOKE BARRIER
 AND CLARIFY WHY THERE IS A FS SYMBOL AT THE EMERGENCY
 CALL PANEL LOCATION. I AM NOT SEEING A DUCT OR A
 TRANSFER ALTHOUGH THE NOTE ON THE SHEET IS INDICATING
 TWO DUCT PENETRATIONS. CLARIFY HOW AIR IS BEING
 RETURNED FROM THE CORRIDOR, AND PLEASE NOTE THE
 FOLLOWING A) NO RETURN GRILLS OR SUPPLY DIFFUSERS ARE
 SHOWN IN THE
  
 CEILING PLAN ON A106.1 B) THE SMOKE BARRIER WALLS ARE
 NOT SHOWN ON THE CEILING PLAN. C) CORRIDORS SHALL NOT
 BE USED AS RETURN AIR DUCTS- SECTION 601.2.
  
 2) SHOW THE AC SHAFTS ON THE ARCHITECTURAL PLANS AND
 PROVIDE HOURLY FIRE RATING AND ASSEMBLY DETAILS.
  
 3) M-2: SHOW THE THE EXISTING DRYER EXHAUST DUCT RUN
 AND TERMINATION LOCATION. PLEASE NOTE AN INDEPENDENT
 SHAFT IS REQUIRED AND THE EXHAUST DUCTS SHALL NOT RUN
 THROUGH A PLENUM SPACE- SEE SECTION 504.
  
 4) M-4: PROVIDE AN EQUIPMENT SCHEDULE AND INSTALLATION
 FOR THE FIRE/SMOKE DAMPERS. INDICATE IF THE DAMPERS ARE
 STANDARD OR DYNAMIC AND PROVIDE SEQUENCES OF OPERATION.
  
 5) AC COOLING AND HEATING CALCULATIONS NOT PROVIDED FOR
 THE 4TH-6TH FLOOR LOBBIES ALTHOUGH THE PLANS SHOW
 SUPPLY AIR TO THOSE AREAS.
  
 6) PROVIDE EQUIPMENT SCHEDULES FOR ALL AC SYSTEMS SHOWN
 OR REFERENCED ON THE PLANS.
  
 7) SHOW THE LOCATION OF THE AIR HANDLER SUPPLYING THE
 LOBBIES AND STORAGE ROOMS, AND PROVIDE SUPPLY CFMS AT
 ALL DIFFUSERS ND GRILLS SHOWN IN THOSE AREAS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  