| Plan Review Notes For Permit 16080543 |
| Permit Number |
16080543 |
|
| Review Stop |
FIRE |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-01-04 09:57:01 | 2210 NORTH AUSTRALIAN AVENUE | | | PERMIT #16080543 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 3RD REVIEW COMMENTS: | | | REPEAT COMMENT - THE FIRST FLOOR ALF SLEEPING AREAS ARE | | | NOT DIVIDED INTO TWO SMOKE COMPARTMENTS. THIS WILL | | | AFFECT ALL TRADES. | | | | | | FIRE ALARM: HOW WILL 75DB AT THE PILLOW BE ACHIEVED | | | WITH NOTIFICATION APPLIANCES LOCATED ONLY IN THE COMMON | | | CORRIDORS? | | | | | | SHEET FA-5: DESIGN INDICATES THE BUILDING WILL BE | | | EVACUATED DURING GENERAL FIRE ALARM. THIS EVACUATION | | | CONCEPT IS NOT SUPPORTED BY THE LIFE SAFETY CODE. THE | | | CODE REQUIRES ASSISTED LIVING FACILITIES TO BE PROVIDED | | | WITH AT LEAST TWO SMOKE COMPARTMENTS PER FLOOR TO ALLOW | | | "DEFEND IN PLACE" WHEREBY RESIDENTS ARE RELOCATED TO AN | | | ADJACENT SMOKE COMPARTMENT DURING A FIRE ALARM. THE | | | FIRE ALARM DRAWINGS NEED GREATER DETAIL TO SHOW | | | COMPLIANCE WITH THIS CONCEPT. HOW IS THE FIRE ALARM, | | | FIRE SPRINKLER (FLOW SWITCHES) AND HVAC (FIRE/SMOKE | | | DAMPERS) BEING INTEGRATED TO ALLOW DEFEND IN PLACE | | | SMOKE COMPARTMENTATION? | | | | | | SHEET FA-5: PLANS INDICATE THIS IS A NEW MERCANTILE | | | OCCUPANCY. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | |
|