| 2016-10-12 12:28:09 | 2ND REVIEW FBC-2014 MECHANICAL |
| | PERMIT #16080543 |
| | 10/12/16 |
| | |
| | 1) SHEET A102.1: THE REVISED PLAN INDICATES A |
| | VENTILATION RATE OF 5 CFM PER PERSON FOR AN ( I-1 |
| | DORMITORY), HOWEVER THE CLASSIFICATION (I-1 DORMITORY) |
| | IS NOT FOUND IN TABLE 403.3. DORMITORY IS GROUPED WITH |
| | HOTELS AND MOTELS IN THE TABLE. PLEASE REFER TO TO |
| | SECTION 308.3 FBC-14 BUILDING WHERE EXAMPLES OF I-1 |
| | FACILITES ARE SHOWN TO INCLUDE ASSISTED LIVING, |
| | CONGREGATE CARE, AND CONVALESCENT CARE FACILITIES. |
| | PLEASE PROVIDE THE APPROPRIATE VENTILATION RATE FOR THE |
| | NEW I-1 FACILITY THAT IS MOST SIMILAR TO THE USE |
| | CLASSIFICATIONS IN THE TABLE I.E. PATIENT ROOMS AT 25 |
| | CFMS PER PERSON OR RESIDIENTIAL LIVING AREAS AT 15 CFM |
| | PER PERSON. PLEASE THEN PROVIDE THE CALCULATIONS FOR |
| | ALL ROOMS AND SPACES ON THE PLAN INCLUDING A SCHEDULE |
| | THAT INDICATES THE "REQUIRED" AND "PROVIDED" CFMS OF |
| | OUTDOOR AIR AND EXHAUST. IDENTIFY WHICH SYSTEMS ARE |
| | PROVIDING THE AIR AND EXHAUST INCLUDING COOLING AND |
| | HEATING AND SUPPLY CFM CAPACITIES FOR EACH AC SYSTEM, |
| | AND CFM CAPACITIES FOR ALL EXHAUST SYSTEMS. |
| | |
| | 2) PLEASE SHOW THE EXISTING AC DUCT LAYOUTS ON ALL |
| | FLOORS INCLUDING: A) DUCT, DIFFUSER, AND GRILL SIZES. |
| | B) LOCATIONS OF ALL FIRE AND FIRE/SMOKE DAMPERS, AND |
| | DUCT SMOKE DETECTORS. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 561-805-6719 |