2016-10-12 14:59:422210 NORTH AUSTRALIAN AVENUE
 PERMIT #16080543
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 2ND REVIEW COMMENTS
 THESE DRAWINGS ARE PUBLIC RECORD FOR SHOWING COMPLIANCE
 AS A NEW ASSISTED LIVING FACILITY. WHILE MANY FIRE AND
 LIFE SAFETY FEATURES MAY BE EXISTING, A FULL AND
 COMPLETE SET OF ARCHITECTURAL AND ENGINEERING PLANS ARE
 NEEDED (ELECTRICAL, MECHANICAL, FIRE ALARM, FIRE
 SPRINKLER, ETC.). IT IS HIGHLY RECOMMENDED THAT THE
 DESIGN TEAM HAS EXPERIENCE WITH THIS TYPE OF OCCUPANCY.
  
 THE FIRST FLOOR ALF SLEEPING AREAS ARE NOT DIVIDED INTO
 TWO SMOKE COMPARTMENTS.
  
 THE FIRE ALARM, FIRE SPRINKLER AND HVAC SYSTEMS ARE
 REQUIRED TO BE ZONED WITH EACH SMOKE COMPARTMENT.
  
 TO OBTAIN A GENERAL BUILDING PERMIT, SIGNED AND SEALED
 ENGINEERING CONSTRUCTION DOCUMENTS ARE NEEDED TO SHOW
 EMERGENCY LIGHTING LOCATIONS AND MODIFICATIONS TO THE
 SMOKE ALARMS, FIRE ALARM, FIRE SPRINKLER AND HVAC
 SYSTEMS.
  
 SOME WALL REFERENCES INDICATE "FIRE AND SMOKE BARRIER
 PARTITION." THIS DESCRIPTION IS INCORRECT. IT IS EITHER
 A PARTITION OR A BARRIER.
  
 HVAC DAMPERS AND DOORS IN SMOKE BARRIERS ARE REQUIRED
 TO RESIST THE PASSAGE OF SMOKE IN ADDITION TO HAVING A
 FIRE RESISTANCE RATING.
  
 UL ASSEMBLIES: THE UL ASSEMBLY DETAILS ARE BARELY
 READABLE AND THE WALL TYPES AND LOCATIONS ARE NOT
 REFERENCED ON THE PLANS.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
  
 ORIGINAL REVIEW COMMENTS
 PER FFPC 101-32.3.3.4.7 APPROVED SMOKE ALARMS SHALL BE
 INSTALLED INSIDE EVERY SLEEPING ROOM, OUTSIDE EVERY
 SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE
 BEDROOMS, AND ON ALL LEVELS WITHIN A RESIDENT UNIT.
  
 PER FFPC 101-32.3.3.4.8.1 CORRIDORS AND SPACES OPEN TO
 THE CORRIDORS SHALL BE PROVIDED WITH SMOKE DETECTORS
 THAT COMPLY WITH NFPA 72, NATIONAL FIRE ALARM AND
 SIGNALING CODE, AND ARE ARRANGED TO INITIATE AN ALARM
 THAT IS AUDIBLE IN ALL SLEEPING AREAS.
  
 PER FFPC 101-32.3.3.7 BUILDINGS SHALL BE SUBDIVIDED BY
 SMOKE BARRIERS. EVERY STORY SHALL BE DIVIDED INTO NOT
 LESS THAN TWO SMOKE COMPARTMENTS. SMOKE BARRIERS SHALL
 HAVE A MINIMUM 1-HOUR FIRE RESISTANCE RATING,
  
 PER FFPC 101-32.3.3.7.15 CROSS-CORRIDOR OPENINGS IN
 SMOKE BARRIERS SHALL BE PROTECTED BY A PAIR OF SWINGING
 DOORS OR A HORIZONTAL-SLIDING DOOR. VISION PANELS
 CONSISTING OF FIRE-RATED GLAZING OR WIRED GLASS PANELS
 IN APPROVED FRAMES SHALL BE PROVIDED IN EACH
 CROSS-CORRIDOR SWINGING DOOR AND IN EACH CROSS-CORRIDOR
 HORIZONTAL-SLIDING DOOR IN A SMOKE BARRIER.
  
 BUILDING IS PROTECTED WITH AN AUTOMATIC SPRINKLER
 SYSTEM. SPRINKLERS ARE REQUIRED TO BE QUICK RESPONSE OR
 RESIDENTIAL STYLE. PLEASE CONFIRM.
  
 A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED
 AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON
 THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED DURING PLAN RESUBMISSION.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  