| 2016-10-12 14:59:42 | 2210 NORTH AUSTRALIAN AVENUE |
| | PERMIT #16080543 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | 2ND REVIEW COMMENTS |
| | THESE DRAWINGS ARE PUBLIC RECORD FOR SHOWING COMPLIANCE |
| | AS A NEW ASSISTED LIVING FACILITY. WHILE MANY FIRE AND |
| | LIFE SAFETY FEATURES MAY BE EXISTING, A FULL AND |
| | COMPLETE SET OF ARCHITECTURAL AND ENGINEERING PLANS ARE |
| | NEEDED (ELECTRICAL, MECHANICAL, FIRE ALARM, FIRE |
| | SPRINKLER, ETC.). IT IS HIGHLY RECOMMENDED THAT THE |
| | DESIGN TEAM HAS EXPERIENCE WITH THIS TYPE OF OCCUPANCY. |
| | |
| | THE FIRST FLOOR ALF SLEEPING AREAS ARE NOT DIVIDED INTO |
| | TWO SMOKE COMPARTMENTS. |
| | |
| | THE FIRE ALARM, FIRE SPRINKLER AND HVAC SYSTEMS ARE |
| | REQUIRED TO BE ZONED WITH EACH SMOKE COMPARTMENT. |
| | |
| | TO OBTAIN A GENERAL BUILDING PERMIT, SIGNED AND SEALED |
| | ENGINEERING CONSTRUCTION DOCUMENTS ARE NEEDED TO SHOW |
| | EMERGENCY LIGHTING LOCATIONS AND MODIFICATIONS TO THE |
| | SMOKE ALARMS, FIRE ALARM, FIRE SPRINKLER AND HVAC |
| | SYSTEMS. |
| | |
| | SOME WALL REFERENCES INDICATE "FIRE AND SMOKE BARRIER |
| | PARTITION." THIS DESCRIPTION IS INCORRECT. IT IS EITHER |
| | A PARTITION OR A BARRIER. |
| | |
| | HVAC DAMPERS AND DOORS IN SMOKE BARRIERS ARE REQUIRED |
| | TO RESIST THE PASSAGE OF SMOKE IN ADDITION TO HAVING A |
| | FIRE RESISTANCE RATING. |
| | |
| | UL ASSEMBLIES: THE UL ASSEMBLY DETAILS ARE BARELY |
| | READABLE AND THE WALL TYPES AND LOCATIONS ARE NOT |
| | REFERENCED ON THE PLANS. |
| | |
| | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| | AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| | THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED DURING PLAN RESUBMISSION. |
| | |
| | |
| | ORIGINAL REVIEW COMMENTS |
| | PER FFPC 101-32.3.3.4.7 APPROVED SMOKE ALARMS SHALL BE |
| | INSTALLED INSIDE EVERY SLEEPING ROOM, OUTSIDE EVERY |
| | SLEEPING AREA IN THE IMMEDIATE VICINITY OF THE |
| | BEDROOMS, AND ON ALL LEVELS WITHIN A RESIDENT UNIT. |
| | |
| | PER FFPC 101-32.3.3.4.8.1 CORRIDORS AND SPACES OPEN TO |
| | THE CORRIDORS SHALL BE PROVIDED WITH SMOKE DETECTORS |
| | THAT COMPLY WITH NFPA 72, NATIONAL FIRE ALARM AND |
| | SIGNALING CODE, AND ARE ARRANGED TO INITIATE AN ALARM |
| | THAT IS AUDIBLE IN ALL SLEEPING AREAS. |
| | |
| | PER FFPC 101-32.3.3.7 BUILDINGS SHALL BE SUBDIVIDED BY |
| | SMOKE BARRIERS. EVERY STORY SHALL BE DIVIDED INTO NOT |
| | LESS THAN TWO SMOKE COMPARTMENTS. SMOKE BARRIERS SHALL |
| | HAVE A MINIMUM 1-HOUR FIRE RESISTANCE RATING, |
| | |
| | PER FFPC 101-32.3.3.7.15 CROSS-CORRIDOR OPENINGS IN |
| | SMOKE BARRIERS SHALL BE PROTECTED BY A PAIR OF SWINGING |
| | DOORS OR A HORIZONTAL-SLIDING DOOR. VISION PANELS |
| | CONSISTING OF FIRE-RATED GLAZING OR WIRED GLASS PANELS |
| | IN APPROVED FRAMES SHALL BE PROVIDED IN EACH |
| | CROSS-CORRIDOR SWINGING DOOR AND IN EACH CROSS-CORRIDOR |
| | HORIZONTAL-SLIDING DOOR IN A SMOKE BARRIER. |
| | |
| | BUILDING IS PROTECTED WITH AN AUTOMATIC SPRINKLER |
| | SYSTEM. SPRINKLERS ARE REQUIRED TO BE QUICK RESPONSE OR |
| | RESIDENTIAL STYLE. PLEASE CONFIRM. |
| | |
| | A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| | AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| | THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED DURING PLAN RESUBMISSION. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |