| 2016-10-13 16:05:34 | 2ND REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | 1] PROVIDE EMERGENCY LIGHTING FOR MEANS OF EGRESS IN | | | EXIT STAIRS AND HALLWAYS. THE ILLUMINATION LEVEL SHALL | | | NOT BE LESS THAN 1' CANDLE AT THE WALKING SURFACE. | | | FBC-1006 | | | NOT ADDRESSED, SHOW EMERGENCY LIGHTS ON FLOORS 1-6. | | | | | | 2] EXIT SIGNS PLACEMENT SHALL BE SUCH THAT NO POINT IN | | | AN EXIT ACCESS CORRIDOR OR EXIT PASSAGEWAY IS MORE THAN | | | 100'. ADD DIRECTIONAL ARROWS WHERE NECCESSARY. FBC-1011 | | | NOT ADDRESSED, SHOW EXITS ON FLOORS 1-6. | | | | | | 3] THIS COMMENT WAS ADDRESSED WITH BLOCK NOTE. | | | | | | 4] NEW COMMENT, PLEASE COMPY WITH FIRE REVIEWERS | | | REQUEST TO SHOW FIRE ALARM DEVICE LOCATION. |
|