| Plan Review Notes For Permit 16080543 |
| Permit Number |
16080543 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-23 17:20:27 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING, | | | ENERGY CODES | | | PERMIT #16080543 | | | 8/23/16 | | | | | | 1) THE PLANS INDICATE A CHANGE OF OCCUPANCY AS DEFINED | | | IN SECTION 202 FBC-14 EXISTING BUILDING CODE. PLEASE | | | SEE SECTION 1009.1 FBC-14 AND PROVIDE VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES, INCLUDING | | | EXHAUST VENTILATION WHERE REQUIRED. | | | | | | 2) REFER TO SECTION C101.4.4 FBC-14 ENERGY | | | CONSERVATION: CHANGE IN OCCUPANCY OR USE. | | | SPACES UNDERGOING A CHANGE IN OCCUPANCY THAT WOULD | | | RESULT IN AN INCREASE IN DEMAND FOR EITHER FOSSIL FUEL | | | OR ELECTRICAL ENERGY SHALL COMPLY WITH THIS CODE. WHERE | | | THE USE IN A SPACE CHANGES FROM ONE USE IN TABLE | | | C405.5.2(1) OR (2) TO ANOTHER USE IN TABLE C405.5.2(1) | | | OR (2), THE INSTALLED LIGHTING WATTAGE SHALL COMPLY | | | WITH SECTION C405.5. | | | | | | PLEASE NOTE ENERGY CALCULATIONS MAY BE REQUIRED- SEE | | | SECTION C101.5.1 FOR COMPLIANCE MATERIALS. | | | | | | 3) PROVIDE MECHANICAL PLANS INDICATING ALL PROPOSED | | | ALTERATIONS TO THE EXISTING SYSTEMS (IF APPLICABLE). | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|