| Plan Review Notes For Permit 16080543 |
| Permit Number |
16080543 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-22 10:11:17 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | 1] PROVIDE EMERGENCY LIGHTING FOR MEANS OF EGRESS IN | | | EXIT STAIRS AND HALLWAYS. THE ILLUMINATION LEVEL SHALL | | | NOT BE LESS THAN 1' CANDLE AT THE WALKING SURFACE. | | | FBC-1006 | | | | | | 2] EXIT SIGNS PLACEMENT SHALL BE SUCH THAT NO POINT IN | | | AN EXIT ACCESS CORRIDOR OR EXIT PASSAGEWAY IS MORE THAN | | | 100'. ADD DIRECTIONAL ARROWS WHERE NECCESSARY. FBC-1011 | | | (RED-LINED ON PLANS) | | | | | | 3] NEC 700.12 (F) (4) ? EMERGENCY/EXIT LIGHTING SHALL | | | BE FED BY LIGHTING CIRCUIT OF SAME LOCAL AREA. *IF 3 OR | | | MORE LIGHTING CIRCUITS SUPPLY THE AREA, EM LIGHTS MAY | | | BE ON OWN CIRCUIT. |
|