| Plan Review Notes For Permit 16080524 |
| Permit Number |
16080524 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-18 14:09:23 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | 1) PROVIDE GFCI PROTECTION FOR THE KITCHEN COUNTER-TOP | | | RECEPTACLES. NEC 210.8.A.6 [ADD TO OUTLET SYMBOL] | | | | | | 2) TAMPER-RESISTANT RECEPTACLES REQUIRED PER NEC 406.12 | | | [ADD A NOTE] | | | | | | 3) SMOKE ALARMS REQUIRED PER FBC-R 314 & 315. IF | | | EXISTING MAKE A NOTE |
|