2016-08-22 13:58:081ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080512
 8/22/16
  
 1) THE SUBMITTED HOOD PLANS ARE NOT ACCEPTABLE FOR
 APPROVAL IN THE STATE OF FLORIDA BECAUSE THEY BEAR THE
 TITLE BLOCK AND RAISED SEAL AND SIGNATURE OF NEW JERSEY
 PE STEVEN SCHENEIDER. PLEASE REFER TO SECTION 105.3.1.2
 WPB AMENDMENTS TO THE FBC AND PROVIDE PLANS AND
 SPECIFICATIONS DESIGNED BY A FL. LICENSED ENGINEER- SEE
 CHAPTER 471 FLORIDA STATUES AND SECTION 61G-15-23.002
 FLORIDA ADMINISTRATIVE CODE.
  
 2) THE SUBMITTED PLANS SHOWING FOUR HOODS DOES NOT
 MATCH WITH THE MAIN PLANS UNDER PERMIT #14120908 WHICH
 INDICATES ONLY TWO- PLEASE REVISE THE PLAN,
 SPECIFICATIONS, SCHEDULES, AND AIR BALANCE CALCULATIONS
 ETC. TO MATCH.
  
 3) GENERAL NOTE #1 LISTED ON THE SUBMITTED PLANS
 INDICATES THE HOODS ARE DESIGNED AT EXHAUST CAPACITIES
 OF 250 AND 280 CFRMS WHICH IS "LIGHT-DUTY" PER SECTION
 507.13. PLEASE PROVIDE AN EQUIPMENT LIST FOR THE
 COOKING APPLIANCES AND MANUFACTURER'S SPECIFICATIONS-
 SEE SECTION 202 FOR DEFINITIONS OF LIGHT, MEDIUM,
 HEAVY, AND EXTRA-HEAVY DUTY APPLIANCES.INDICATRE WHICH
 APPLIANCES WILL BE UNDER EACH HOOD.
  
 4) IN ORDER TO HELP EXPEDITE THE PROPOSED PROJECT,
 PLEASE PROVIDE A NARRATIVE RESPONSE FROM THE DESIGN
 PROFESSIONAL OF RECORD.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  