| Date |
Text |
| 2016-09-23 15:49:47 | 2471 OKEECHOBEE BOULEVARD |
| | PERMIT #16080511 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | REPEAT COMMENT: ENGINEERED FIRE ALARM AND FIRE |
| | SPRINKLER CONSTRUCTION DOCUMENTS ARE REQUIRED FOR A |
| | GENERAL BUILDING PERMIT. AFTER THE BUILDING PERMIT HAS |
| | BEEN ISSUED, THE SUBCONTRACTORS CAN THEN SUBMIT SHOP |
| | DRAWINGS (CONFORMING TO THE ENGINEERED CONSTRUCTION |
| | DOCUMENTS) FOR A SUB-PERMIT. |
| | |
| | ADDITIONAL INFORMATION: FOR ISSUANCE OF A GENERAL |
| | BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE FLORIDA |
| | BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| | 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. PER FBC SECTION 907.1.1 |
| | CONSTRUCTION DOCUMENTS - CONSTRUCTION DOCUMENTS FOR |
| | FIRE ALARM SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO |
| | INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE, THE FLORIDA FIRE PREVENTION |
| | CODE, AND RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |