| Plan Review Notes For Permit 16080511 |
| Permit Number |
16080511 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-23 15:46:03 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080511 | | | 8/23/16 | | | | | | 1) THE INSTALLED EFFICIENCIES LISTED ON THE SUBMITTED | | | ENERGY FORM C402 DO NOT MATCH EFFICIENCIES LISTED IN | | | THE EQUIPMENT SCHEDULES. | | | | | | 2) FORM C402 MUST BE SIGNED AND DATED BY THE | | | OWNER/AGENT. | | | | | | 3) THE COOLING AND HEATING CAPACITIES OF RTU'S 5 & 6 | | | EXCEED THE CALCULATED LOADS SUBMITTED- SEE SECTION | | | C403.2.2 FBC-14 ENERGY CONSERVATION. | | | | | | 4) M-1: PLEASE ENLARGE THE RTU DETAILS SO THAT THE | | | SMOKE DETECTOR AND CO2 DETECTORS ARE VISIBLE. | | | | | | 5) M-2: INDICATE HOW THE SD'S AND CO2 SENSORS WILL BE | | | INSTALLED IN THE STEP DOWN DIFFUSER DETAIL. | | | | | | 6) PROVIDE A SEQUENCE OF OPERATION FOR THE CO2 SENSORS | | | AND SUBMIT MANUFACTURER'S SPECIFICATIONS WITH APPROVAL | | | SIGNATURE BY THE EOR. | | | | | | 7) PROVIDE WIND LOAD DESIGN CRITERIA AND COMPLETE | | | DETAILS FOR ANCHORING THE RTU'S, CURBS, AND CURB | | | ADAPTERS TO THE ROOF STRUCTURE- SECTION 301.15. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|