2016-08-23 15:46:031ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16080511
 8/23/16
  
 1) THE INSTALLED EFFICIENCIES LISTED ON THE SUBMITTED
 ENERGY FORM C402 DO NOT MATCH EFFICIENCIES LISTED IN
 THE EQUIPMENT SCHEDULES.
  
 2) FORM C402 MUST BE SIGNED AND DATED BY THE
 OWNER/AGENT.
  
 3) THE COOLING AND HEATING CAPACITIES OF RTU'S 5 & 6
 EXCEED THE CALCULATED LOADS SUBMITTED- SEE SECTION
 C403.2.2 FBC-14 ENERGY CONSERVATION.
  
 4) M-1: PLEASE ENLARGE THE RTU DETAILS SO THAT THE
 SMOKE DETECTOR AND CO2 DETECTORS ARE VISIBLE.
  
 5) M-2: INDICATE HOW THE SD'S AND CO2 SENSORS WILL BE
 INSTALLED IN THE STEP DOWN DIFFUSER DETAIL.
  
 6) PROVIDE A SEQUENCE OF OPERATION FOR THE CO2 SENSORS
 AND SUBMIT MANUFACTURER'S SPECIFICATIONS WITH APPROVAL
 SIGNATURE BY THE EOR.
  
 7) PROVIDE WIND LOAD DESIGN CRITERIA AND COMPLETE
 DETAILS FOR ANCHORING THE RTU'S, CURBS, AND CURB
 ADAPTERS TO THE ROOF STRUCTURE- SECTION 301.15.
  