2016-08-15 15:15:05JOB PERMIT NUMBER: 16080511
 JOB ADDRESS: 2471 OKEECHOBEE BLVD
 WEST PALM BEACH FLORIDA, SUITE PS
 DATE: AUGUST 15, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
 THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION
 HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF
 THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC,
 (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST
 PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF
 SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED.
  
 1) FIRE ALARM AND LOW VOLTAGE SHALL BE UNDER A SEPARATE
 PERMIT WITH SEPARATE SHOP DRAWINGS. [ INFORMATIONAL
 NOTE ]
 2) PROVIDE FPL AVAILABLE FAULT CURRENT LETTER AND
 DEMONSTRATE AIC RATING OF OVERCURRENT DEVICES PLUS SC
 RATING OF EQUIPMENT TO WITHSTAND L+L, L+N, AND GROUND
 FAULTS LIKELY TO BE IMPOSED ONTO THE ELECTRICAL SYSTEM.
 NEC 110.9, 110.10, 110.24(A)(B)
 3) SHEET E-1, CLARIFY HOW PANEL ??DP?? SHOWS A 60 AMP
 PROTECTIVE DEVICE FOR PANEL ?A? WHEN THE DEMANDED LOAD
 IS 69 AMPS ? FBC-107
 4) SHEET E-1, SHOW EXISTING SERVICE CONDUCTOR SIZE WITH
 INSULATION RATING AND SPECIFY HOW THE CONNECTION WITHIN
 THE EXISTING SERVICE DISCONNECT IS GOING TO BE
 MECHANICALLY MADE, FURTHERMORE APPLY ADEQUATE WARNING
 LABELING TO THE ENCLOSURE FOR FEED THRU UNFUSED LINES.
 FBC-107, NEC 110.12
 5) SHEET E-1, FEEDER SCHEDULE REFLECTS THE SERVICE
 BEING PARALLELED IN 3 RACEWAYS, IS THE INTENT 2
 RACEWAYS ? IF NOT SPECIFY EQUIPMENT TO BE IDENTIFIED
 FOR MULTI-TERMINAL PARTS TO ENSURE A GOOD CONNECTION
 WITHOUT DAMAGING THE CONDUCTORS. NEC 110.14(A)
 6) PROVIDE LIGHT DENSITY CHART FOR MAXIMUM ENERGY
 ALLOWANCES IN THE BUILDING SPACE. FBC-E SECTION C405.5
 INTERIOR LIGHTING POWER REQUIREMENTS.
 7) FBC-E C405.7.3 VOLTAGE DROP. FEEDERS & CUSTOMER
 OWNED SERVICE CONDUCTORS SHALL BE SIZED FOR A MAXIMUM
 OF 2% VOLTAGE DROP. BRANCH CIRCUITS SHALL BE SIZED FOR
 A MAXIMUM OF 3% VOLTAGE DROP. ADD THIS CODE LANGUAGE ON
 SHEET E-3 GENERAL NOTE G.
 8) FBC-E SECTION C405.7 A MINIMUM OF 50% OF ALL 125V,
 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED WHERE INSTALLED IN PRIVATE OR PEN OFFICES,
 COMPUTER CLASSROOMS, AND MODULAR PARTITIONS. [ ADD A
 NOTE TO COMPLY. ]
 9) NEC 406.3(D) RECEPTACLES INCORPORATING AN ISOLATING
 GROUNDING CONDUCTOR CONNECTION INTENDED FOR THE
 REDUCTION OF ELECTRICAL NOISE SHALL BE IDENTIFIED BY AN
 ORANGE TRIANGLE ON THE FACE OF THE FACEPLATE. [ A NOTE
 WILL SUFFICE ]
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED DEFICIENCIES.WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, YOU ARE REQUIRED TO
 PROVIDE A RESPONSE LETTER (NARRATIVE) ADDRESSING EACH
 ITEM ALONG WITH THE STANDARD CITY RE-SUBMITTAL FORM.
 THE NARRATIVE SHOULD INCLUDE THE PLAN REVIEWER?S
 COMMENTS AND YOUR RESPONSE OR ACTION TO SAME.
 ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE
 SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARISON.
 CLOUDING THE CHANGES WILL BE GREATLY APPRECIATED. IF
 YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713