| Plan Review Notes For Permit 16080482 |
| Permit Number |
16080482 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-23 14:03:08 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #16080482 | | | 8/23/16 | | | | | | 1) SHEET 3.0 MP:THE 14X6" SUPPLY TRUNKS ARE UNDERSIZED | | | FOR 600 CFMS EACH- MINIMUM SIZE REQUIRED IS 14X8" BASED | | | ON THE ASHRAE HANDBOOK OF FUNDAMENTALS. | | | | | | 2) 3.0 MP: PLEASE CORRECT THE FRESH AIR CALCULATION | | | SPECIFYING 2000 CFMS REQUIRED FOR THE KITCHEN. REFER TO | | | TABLE 403.3 WHICH REQUIRES A 0.7 CFM PER SQ. FT. | | | EXHAUST RATE FOR THE KITCHEN. | | | | | | 3) 3.0 MP: PLEASE CLARIFY THE PURPOSE OF THE 6" | | | MOTORIZED DAMPER SHOWN IN THE DINNIG ROOM. WHICH SYSTEM | | | IS THE DAMPER CONNECTED TO. | | | | | | 6) 3.0 MP: BASED ON ASHRAE STANDARD RETURN GRILL SIZING | | | - 2CFMS PER SQ. IN., THE 30X8" RETURN GRILL HAS AN | | | INSUFFICIENT CAPACITY OF 580 CFMS- PLEASE ENLARGE THE | | | GRILL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|