Plan Review Notes
Plan Review Notes For Permit 16080477
Permit Number 16080477
Review Stop M
Sequence Number 3
Notes
Date Text
2016-09-13 16:02:15RESIDENTIAL REVISION, THIRD MECHANICAL CHECKLIST.
 CODE: FBC 5TH EDITION (2014).
  
 ORIGINAL COMMENT.
 1- THE MASTER BEDROOM AND BEDROOM #1 ON THE SECOND
 FLOOR DON'T COMPLY WITH THE BALANCED RETURN AIR SEC.
 M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). THE
 TRANSFER GRILLES (14"X6") ARE TOO SMALL BASED ON THE
 SUPPLY AIR. NOTE: THE MASTER BEDROOM NEEDS TO CONSIDER
 ALL THE SUPPLY AIR, INCLUDING THE CLOSET AND BATHROOM.
 SEE EXCEPTIONS #2 AND #3 OF SEC M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE PLANS AS
 REQUIRED.
  
 RESPONSE:
 (1) ALL THE SUPPLY AIR INTO THE MASTER BEDROOM,
 INCLUDING CLOSET AND BATHROOM NEEDS TO BE CONSIDERED TO
 SIZE THE TRANSFER GRILL. 24"X6" TRANSFER GRILL DOESN'T
 COMPLY. SEE EXCEPTION #2 AND #3 OF SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE AS
 REQUIRED.
  
 (2) TRANSFER GRILLES AND TRANSFER DUCTS ARE NOT THE
 SAME. TRANSFER GRILL SIZE IS NOT DETERMINED BY THE
 1-1/2 TIMES THE CROSS SECTIONAL AREA. SEE EXCEPTION #1
 AND #2 OF SEC. M1602.4 FBC-RESIDENTIAL, 5TH EDITION
 (2014). 14"X6" TRANSFER GRILL SPECIFIED FOR BEDROOM #1
 DOESN'T COMPLY. REVISE SIZE OF TRANSFER GRILL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  
  