| 2016-08-22 17:39:52 | RESIDENTIAL REVISION, MECHANICAL SECOND CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | |
| | 1- THE SITTING ROOM ON THE FIRST FLOOR DOESN'T COMPLY |
| | WITH THE BALANCED RETURN AIR SEC. M1602.4 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE PLAN AS |
| | REQUIRED. |
| | |
| | 2- THE MASTER BEDROOM AND BEDROOM #1 ON THE SECOND |
| | FLOOR DON'T COMPLY WITH THE BALANCED RETURN AIR SEC. |
| | M1602.4 FBC-RESIDENTIAL, 5TH EDITION (2014). THE |
| | TRANSFER GRILLES (14"X6") ARE TOO SMALL BASED ON THE |
| | SUPPLY AIR. NOTE: THE MASTER BEDROOM NEEDS TO CONSIDER |
| | ALL THE SUPPLY AIR, INCLUDING THE CLOSET AND BATHROOM. |
| | SEE EXCEPTIONS #2 AND #3 OF SEC M1602.4 |
| | FBC-RESIDENTIAL, 5TH EDITION (2014) AND REVISE PLANS AS |
| | REQUIRED. |
| | |
| | 3- A/C COMPRESSOR DETAIL SPECIFIES FLORIDA PRODUCT |
| | APPROVAL FL14239 FOR THE HOLD DOWN CLIPS. INFORMATION |
| | SPECIFIED DON'T MATCH INFORMATION SHOWN ON THE FLORIDA |
| | PRODUCT APPROVAL. REVISE CONNECTORS TYPE, SIZE, |
| | EMBEDMENT INTO CONCRETE AND CORNER DISTANCE. SEE |
| | PRODUCT APPROVAL AND REVISE AS REQUIRED. SEC.R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 4- PLANS NEED THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN AS REQUIRED BY SEC. 107.2.1 |
| | CITY AMENDMENTS. |
| | |