| Plan Review Notes For Permit 16080459 |
| Permit Number |
16080459 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-09-13 13:15:09 | 2ND REVIEW: FBC 2014 5TH ED. | | | 16080459 - 401 N FLAGLER DR | | | | | | FAILED. | | | | | | PREVIOUS COMMENTS COMPLIED, HOWEVER THE SUBMITTED | | | PRECAST ENGINEERED DRAWINGS SHOW 8'0" HIGH WALLS. THE | | | PLAN SHOWS 10'0" HIGH WALLS | | | | | | PROVIDE PRECAST WALLS ENGINEERED DRAWING FROM | | | MANUFACTURER. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | | | 2016-08-17 10:49:38 | 1ST REVIEW: FBC 2014 5TH ED. | | | 16080459 - 401 N FLAGLER DR | | | | | | PLEASE BE MORE SPECIFIC AS TO THE PERMIT DESCRIPTION VS | | | THE IMPROVEMENTS INTENDED FOR THIS APPLICATION. THE | | | DESCRIPTION SHOULD BE AS FOLLOWS: " INSTALLATION OF 5- | | | 10'X8' WALLS" AND ANY OTHER ASSOCIATED IMPROVEMENTS | | | SUCH AS AN ACCESSIBLE PAVED ROUT," THE DESCRIPTION AS | | | STATED IS VAGUE AND THE PLAN SHOWS ITEMS 1, 2, 3, & 4 | | | IN THE "KIDS ART PARK" WITHOUT SUFFICIENT DETAIL TO | | | ASCERTAIN IF CONSTRUCTION IMPROVEMENTS ARE INTENDED | | | THERE AS PART OF THIS APPLICATION. | | | | | | IF IT IS INTENDED FOR THE WORK TO BE VIEWED UP CLOSE BY | | | THE PUBLIC WALKING UPON THE GROUND SURFACE, PLEASE | | | ADDRESS HOW ACCESS WILL BE PROVIDED FOR PERSON IN NEED | | | OF ACCOMMODATION. PROVIDE ACCESSIBLE ROUTE DETAILS PER | | | FBC 107. | | | | | | PLEASE PROVIDE A SURVEY OR UPDATED SITE PLAN TO | | | INDICATE THE SPECIFIC LOCATION AND ELEVATION OF THE | | | PROPOSED IMPROVEMENTS. | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|