| Plan Review Notes For Permit 16080447 |
| Permit Number |
16080447 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-11 16:07:39 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - PROVIDE NEW PANEL SCHEDULES WITH AVALIUABLE FAULT | | | CURRENTS NEC 110.24, SHORT CIRCUIT RATINGS NEC 110.10 & | | | 110.9, AND LOAD DEMANDS 6LA, 6LB, 6TR. FBC 107 MINIMUM | | | PLAN REVIEW | | | | | | - TRANSFORMER SECONDARY CONDUCTORS SHALL TERMINATE TO | | | AN OCPD IN A PANEL-BOARD PER NEC 408.36(B) OTHERWISE | | | CLARIFY COMPLIANCE WITH NEC 450.3 & 240.21(C). | | | | | | - VALUATION SEEMS TO LOW PROVIDE OWNER SIGNED CONTRACT | | | IN ACCORDANCE WITH FBC-109. | | | | | | - NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL | | | EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO | | | REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED | | | TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS. |
|