2016-08-11 16:07:39REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PROVIDE NEW PANEL SCHEDULES WITH AVALIUABLE FAULT
 CURRENTS NEC 110.24, SHORT CIRCUIT RATINGS NEC 110.10 &
 110.9, AND LOAD DEMANDS 6LA, 6LB, 6TR. FBC 107 MINIMUM
 PLAN REVIEW
  
 - TRANSFORMER SECONDARY CONDUCTORS SHALL TERMINATE TO
 AN OCPD IN A PANEL-BOARD PER NEC 408.36(B) OTHERWISE
 CLARIFY COMPLIANCE WITH NEC 450.3 & 240.21(C).
  
 - VALUATION SEEMS TO LOW PROVIDE OWNER SIGNED CONTRACT
 IN ACCORDANCE WITH FBC-109.
  
 - NEC 110.16 ARC-FLASH HAZARD WARNING: ELECTRICAL
 EQUIPMENT IN OTHER THAN DWELLING UNITS LIKELY TO
 REQUIRE SERVICED WHILE ENERGIZED SHALL BE FIELD MARKED
 TO WARN AGAINST POTENTIAL ARC-FAULT HAZARDS.