| Plan Review Notes For Permit 16080441 |
| Permit Number |
16080441 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-12 10:56:57 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY ELECTRICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT TWO SETS OF LOAD CALCULATIONS AND PANEL | | | SCHEDULES TO SHOW THAT THE EXISTING ELECTRICAL SYSTEM | | | IS CAPABLE OF ACCOMODATING THE POOL EQUIPMENT AND | | | HEATER. FBCR-E3602.2 | | | | | | 2) SHOW COMPLIANCE WITH FBCR - E 4204.3 FOR REQUIRED | | | BONDING OF POOL WATER. | | | | | | |
|