| Plan Review Notes For Permit 16080412 |
| Permit Number |
16080412 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-10-21 07:21:54 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: (PREVIOUS | | | COMMENTS WERE NOT ADDRESSED) | | | | | | 1) SPECIFY THE EXISTING WINDOW TYPES AND SIZES ON THE | | | KEY PLAN. FBC 107.2.1 | | | | | | 2) FBC 107.3.4 - PROVIDE TWO COMPLETE PRODUCT APPROVALS | | | WITH FL OR NOA NUMBERS INCLUDING INSTALLATION | | | INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR THE | | | STRUCTURAL WINDOW MULLIONS. | | | | | | |
|