| Plan Review Notes For Permit 16080410 |
| Permit Number |
16080410 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-09-26 14:08:21 | PLAN | | | REVIEW COMMENTS | | | 3RD REVIEW: FBC FIFTH EDITION (2014) | | | REVIEWED BY ROBERT MCDOUGAL, CBO, FOR JAMES WITMER | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE NOA NUMBER IS MISSING FROM THE NOTES ON PAGE 3 | | | OF THE RAS 117 CALCULATIONS. SEE COMMENTS FROM PREVIOUS | | | REVIEWS. | | | | | | 2) THE WIDTH OF THE THE GAFGLAS #75 BASE SHEET IS | | | 39.37" PER PAGE 2 OF NOA NO. 14-1030.02 RATHER THAN THE | | | 36" SPECIFIED IN THE RAS 117 CALCULATIONS. PLEASE | | | CORRECT AND REVISE CALCULATIONS. | | | | | | 3) ALL THREE PAGES OF RAS 117 CALCULATIONS ARE REQUIRED | | | TO HAVE THE ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE | | | AND SEAL (FACSIMILES ARE NOT ACCEPTABLE). FAC | | | 61G15-23.002 | | | | | | |
|