| 2016-08-24 07:57:04 | ROOFING/ BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16080410 |
| | ADD: 530 32ND ST |
| | CONT: GRACE ROOFING |
| | TEL: 954-733-7332 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: WED. AUGUST 24/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE ENGINEER ANTONIO ACEVEDO HAS MADE A GENERIC FORM |
| | FOR ENHANCED FASTENING. PLEASE SEE THE FORM DOES NOT |
| | LIST THE PRODUCT APPROVAL NUMBER, THE TYPE OF |
| | SUB-SYSTEM , PAGE THE SUB-SYSTEM CAN BE FOUND ON. PAGE |
| | 1 AND PAGE 3 BOTH HAVE AN AREA WHERE THE PRODUCT |
| | APPROVAL NUMBER CAN BE INSERTED (BLANK), BUT THE |
| | SUB-SYSTEM NOR PAGE NOT IDENTIFIED. |
| | |
| | 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE |
| | CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND |
| | DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS, |
| | FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND |
| | RESISTANCE RATING THAT ARE REQUIRED TO BE |
| | INSTALLED. PRODUCT EVALUATION AND INSTALLATION SHALL |
| | INDICATE COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR |
| | THE SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR |
| | ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH |
| | THE CONSTRUCTION DOCUMENTS. |
| | |
| | |
| | |
| | 2) WITHIN THE PRODUCT APPROVALS THE SUB-SYSTEM IS |
| | MARKED VOID IN PENCIL!!! |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |