| Plan Review Notes For Permit 16080405 |
| Permit Number |
16080405 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-30 02:49:24 | 1) SUBMIT A SANITARY AND WATER RISER DIAGRAM FOR ALL | | | THE CHANGES, ADDITIONS AND RELOCATION OF THE PLUMBING | | | PIPING AND FIXTURES. WPB AMEND. TO FBC SEC. | | | 107.3.5.1.3. | | | 2) SUBMIT AN EXISTING FLOOR PLAN FOR THE SECOND FLOOR. | | | WPB AMEND. TO FBC SEC. 107.2.1. | | | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE | | | TANKLESS WATER HEATER.WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) IF THE WASHER/ DRYER IS A STACKED UNIT, ACCESS SHALL | | | BE PROVIDED TO THE WATER SUPPLY VALVES FOR THE WASHER. | | | 2014 FBCR SEC.P2903.9.3. | | | 5) INDICATE ON THE PLAN HOW HOT WATER IS BEING SUPPLIED | | | TO THE GUEST HOUSE. SHOW THE HOT WATER SUPPLY SOURCE. | | | 6) SHT. 1 INDICATES THAT NEW FIXTURES WILL CONNECT TO | | | EXISTING PLUMBING BUT THE FIXTURES ARE BEING RELOCATED. | | | CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|